Section: INSPECT/PREPARE INSTALLATION SITE

Examine the installation site for conditions that could

adversely affect the health and safety of installation

personnel and the user of the appliance or proper

operation of the burner and appliance, and correct any

defects found.

○ The area around the appliance should be

unobstructed and dry.

○ Wiring must be in good condition and meet code

requirements.

○ If the burner is replacing an existing oil burner, old

piping and the tank must be secured or removed to

prevent leakage or unintended deliveries of oil.

○ Local jurisdictions may require removal of oil tanks.

See NFPA-30 flammable and combustible liquids

code for approved procedures.

Inspect Chimney and Vent System

1. Any accumulation of soot or debris in chimney

offsets must be removed

2. Any obstructions such as a protruding joint or a

piece of broken tile wedged in the chimney must be

removed.

3. No other appliance connection should be made to

the same flue pipe.

4. The flue pipe should have an upward pitch toward

the chimney of at least 1/4” per foot of length. It

should fit tightly and should not project into the

chimney, see

Figure 3.

Explosion, Fire,

Asphyxiation Hazard

Wet or dusty environments could lead

to blocked air passages, corrosion

damage to components, impaired

combustion performance and result in

asphyxiation, explosion or fire.

y

This burner is designed for clean, dry

installations.

y

Electrical controls are not protected against rain

or sprayed liquids.

y

Keep the installation clear of dust, dirt, corrosive

vapors, and moisture.

y

Protective covers and frequent maintenance may

be required.

Fire, Smoke &

Asphyxiation Hazard

y

Carefully inspect the chimney,

chimney liner & exhaust vent system.

y

Make sure it is properly sized and in

good working condition.

y

Follow the instructions supplied by

the appliance manufacturer.

y

If a draft regulator is required, it must be a

double-acting type, agency recognized for use

with gas vent systems.

y

The chimney installation and vent sizing

must strictly comply with all applicable codes,

authorities having jurisdiction and the latest

revision of the National Fuel Gas Code (ANSI

Z223.1, or NFPA54) or CAN/CGA B/49 Canada.

Remove any vent damper device.

y

Regulation by these authorities take precedence

over the general instructions provided in this

installation manual.

Figure 3 – Vent Pipe with Draft Regulator

Barometric Draft Control

Flue Pipe Ell

Heating Unit

1/4” per Foot

Minimum

Inspect/Prepare

Installation Site

Indoor Installation