Section: SEQUENCE OF OPERATION

Sequence of Operation

Delayed Ignition,

Explosion, and Fire

Hazards

Use only the Beckett 7590 Control on

the CG4 Burner.

This operation sequence is

typical for operation with a 7590

control. This is the only control approved for use on

the CG4 Gas Power Burner.

Do not start the burner yet.
(Reference

Table 6 )

○ Call for heat, Status LED is turned on.

Control performs safe-start check

If safe-start fails, control locks out.

If safe-start passes, control checks for presence

of flame.

If flame is present, control will enter hold state

until flame is no longer present. Flame LED

and Status LED will flash until flame is no longer

present.

If flame is not present, control will check status of

air proving switch. If switch is closed, (indicating

the pressure switch is stuck) control will enter

lockout.

Table 6 – Operating Sequence

LEDs

Call for Heat

FLAME

MV

STATUS

Status LED

turns on

Motor Start

FLAME

MV

STATUS

Status LED

ON

Pre-purge

FLAME

MV

STATUS

Status LED

Flashes

Ignition

FLAME

MV

STATUS

Status, MV

LEDs On

Run

FLAME

MV

STATUS

Status, MV,

Flame LEDs On

End Call for Heat

FLAME

MV

STATUS

LEDs Off

Timers &

Timings

Pre-purge Timer

1 - 240 Seconds

Ignition Trial

Timer

4 - 15 Seconds

Flame Check

On

On

On

On

On

Motor/Blower

Blower Starts

On

On

On

Off

Air Switch Check

On

Air Switch Closes

On

On

On

Igniter

On

Off

Off

Gas Valve

On

On

Off

○ If the air proving switch is open, the motor will start.

Once the air proving switch closes, pre-purge will begin

(lasting 30 seconds). Pre-purge or ignition timings will

not start until the air proving switch closes.

The air proving switch must close to prove

combustion air is present. If switch fails to close

during the specified period, the control will enter

lockout.

○ When pre-purge is completed, the control turns on the

igniter and the gas valve. MV LED will turn on.

Spark continues until end of ignition timing or

until flame is proved.

○ Once flame is proved, The Flame LED is turned on

and the spark is turned off. The gas valve and MV LED

remain energized.

If flame is not proved, the control will lockout or

enter the inter-trial waiting period. Status LED

will flash rapidly for lockout or slowly for inter-trial

waiting.

If multiple trial logic is used, the control will

complete the trials for ignition

When flame is proved the control will continue in

run mode until the end of the call for heat.

○ When the call for heat is ended, the gas valve, MV

LED, Flame LED, Status LED and motor turn off.

Additional information on control operation is available in

the GeniSys 7590 Control Manual (61981-001).