Page 4: Fire hazard: overheating

background image

4

Section: GENERAL INFORMATION

Professional Installer’s Responsibility:

Professional Service

Required

Failure to follow these instructions

could lead to equipment malfunction

and result in asphyxiation, explosion

or fire.

y

Please read all instructions before proceeding.

Follow all instructions completely.

y

This equipment must be installed, adjusted

and started by a qualified service agency that

is licensed and experienced with all applicable

codes and ordinances and responsible for the

installation and commissioning of the equipment.

y

The installation must comply with all local codes

and ordinances having jurisdiction and the latest

edition of the National Fuel Gas Code ANSI

Z223.1 (NFPA 54) and CAN1-B149.1 in Canada.

Specifications

Concealed damage – If you

discover damage to the burner

or controls during unpacking, notify the carrier at

once and file the appropriate claim forms. Do not

install a burner or control that has been damaged.

Special Requirements:

When contacting Beckett for

service information — Please have the burner serial

number and contractor start-up form available when

calling or writing. You will find the serial number on

the label located on the left rear of the burner. Refer

to

Figure 2.

Table 1 – Burner Specifications

Input Firing Rate

80,000 - 250,000 BTU/hr

Firing Mode

On-Off Only

Fuel

Natural gas - 0.64 specific gravity

LP gas - 1.53 specific gravity

Required Input Gas Supply

Pressure

4.5” WC minimum

14” WC maximum

Input Voltage

120 Vac + 10% / -15%; 60 Hz

Input Current

2.75 A (Run); 12.0 ALR

Gas Valve

24 Vac Dual Seat with integral regulator

set to 3.5” WC for both natural gas and

LP

Burner Control

Beckett 7590D Direct Ignition

Flame Detection

Flame Rectification

Igniter

Beckett 7474001 Gas Igniter

Motor

1/7 Hp; PSC

Combustion Air Proving

Differential Pressure Switch

Weight

55 lbs.

Mounting Orientation

Up to 90° from upright with motor shaft

horizontal

Dimensions

10.3” x 13.1” x 15.8”

Acceptable Ambient

Temperature Range

-40°F to 150°F

Acceptable Ambient Humidity

5% - 95% RH non-condensing

For altitudes higher than 2,000 feet, derate the burner capacity 4%

for each 1,000 feet above sea level.

Burner is not approved for use in 50 Hz applications.

Fire Hazard: Overheating

Should over-heating occur:

y

Shut off the manual gas control to

the appliance.

y

DO NOT shut off power to the

equipment, allow the blower and

pumps to continue running.

ETL listed for use in the US or

Canada per ANSI Z21.17(a) / CSA

2.7(a) For use with natural gas or

propane.

If any of these instructions are not clear,

Call Beckett at

1-800-645-2876

for assistance.

For use only on approved

applications. See

www.

beckettcorp.com/cg4apps for the list of approved

applications.