SERVICE PROCEDURE RE-I

Line Voltage & High Limit (ECO)

Testing

WARNING

High voltage exposure. Use caution when

making voltage checks to avoid personal injury.

Line Voltage Testing

Illustration 2

Illustration 3

1. Turn “OFF” power to water heater.

2. Remove access cover(s) from front of water

heater. Remove insulation and plastic cover

from thermostat.

3. Set multi-meter to volts AC.

4. Turn power “ON” to water heater.

5. Check voltage across terminals L1 & L3

of upper thermostat (see illustration 2).

A) Rated voltage IS present, power to the water

heater is okay.

B) Rated voltage NOT present, Check circuit breaker

at service panel.

ECO reset

button

1. Check voltage across terminals L1 & L4 upper thermostat (see illustration 3).

A) Rated Voltage IS present, ECO is okay.

B) Rated voltage NOT present, proceed to step 2.

2. Turn power “OFF” to water heater and firmly press ECO reset button on thermostat(s). Turn power “ON” and recheck

voltage across terminals L1 & L4 of upper thermostat

(see illustration 3).

A) Rated voltage IS present, the ECO has opened indicating the water in the tank is or has over heater.

Check the following:

1. Thermostat must be in full contact with tank.

2. Be sure heating element(s) is not shorted to ground (see page 15).

3. Proper thermostat operation (see procedures beginning on page 16).

B) Rated voltage NOT present, water in tank may be over heated.

1. If water is hot, turn “OFF” power to water heater and flow water through tank to cool below set point

of upper thermostat. Recheck voltage per step 1.

2. If water is cool, Replace upper thermostat.

Page 14

High Limit (ECO) Testing