Safety Circuit Voltage Trace

Note: This procedure assumes a cold tank.

Step 1.

Remove three screws (Phillips screw driver) from

control access cover on blower and remove

cover.

Safety Circuit Voltage Trace

WARNING

115 volt potential exposure. Use caution making voltage checks to avoid

personal injury.

Control access

cover

Position gas control switch to the “ON”

position and adjust the thermostat dial

to call for heat. Is there 10 to 13VAC

between the red wire leading to the

blower temperature switch and the

green ground wire? Blower must be

running during this voltage check (see

photo 15).

Is LED on gas valve flash-

ing the “heartbeat” code

(alternating bright/dim)?

No voltage from gas control.

Call for technical support.

Verify 115VAC to gas con-

trol (see page 41).

Is there 10 to 13VAC between

the yellow wire leading from the

pressure switch and the green

ground wire (see photo 27)?

Is there continuity through

the blower temperature

switch (see page 31)?

Check for loose or broken

wire connection at switch

terminals.

Do you hear or can you

see the igniter sparking?

Check igniter/sensor (see page

22). Is igniter/sensor OK?

Correct igniter/

sensor problem

Determine cause of blower

temperature switch activa-

tion and correct.

Faulty cord set

or gas control

Safety circuit

voltage is OK.

If burner does not light, ob-

serve LED flash code on gas
control and refer to trouble-

shooting section on page 17.

Green ground wire

Red sire leading to

blower temp. switch

Yellow wire leading

from pressure switch

15

14

N

N

Y

Y

N

Y

N

Y

N

Y

Y