beautypg.com

Oa ) + (tr, Ra ) =t, 48h e, h j – Carrier 48HJ004---007 User Manual

Page 27

background image

27

activation to allow the dampers to open. This delay allows the
damper to reach the appropriate position to avoid unnecessary fan

overload.
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 42.) The minimum damper

position maintains the minimum airflow into the building during

the occupied period.
When using demand ventilation, the minimum damper position

represents the minimum ventilation position for VOC (volatile
organic compound) ventilation requirements. The maximum

demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum
position potentiometer should be used to set the occupied

ventilation position. The maximum demand ventilation position
should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes, to

enter the building. Make minimum position adjustments with at

least 10_F temperature difference between the outdoor and
return-air temperatures.
To determine the minimum position setting, perform the
following procedure:

1. Calculate the appropriate mixed air temperature using the

following formula:

(T

O x

OA

) + (TR

x

RA

) =T

M

100

100

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air

T

R

= Return-Air Temperature

RA = Percent of Return Air
T

M

= Mixed-Air Temperature

As an example, if local codes require 10% outdoor air during
occupied conditions, outdoor-air temperature is 60_F, and

return-air temperature is 75_F.
(60 x .10) + (75 x .90) = 73.5_F

2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across

terminals P and P1. If remote damper positioning is being
used, make sure that the terminals are wired according to

Fig. 36 and that the minimum position potentiometer is
turned fully clockwise.

4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer

until the measured supply air temperature matches the

calculated value.

6. Reconnect the mixed air sensor to terminals T and T1.

Remote control of the EconoMi$er IV damper is desirable when
requiring

additional

temporary

ventilation.

If

a

field-supplied remote potentiometer (Honeywell part number
S963B1128) is wired to the EconoMi$er IV controller, the

minimum position of the damper can be controlled from a remote

location.
To control the minimum damper position remotely, remove the

factory-installed jumper on the P and P1 terminals on the
EconoMi$er IV controller. Wire the field-supplied potentiometer

to the P and P1 terminals on the EconoMi$er IV controller. (See

Fig. 46.)
Damper Movement
Damper movement from full open to full closed (or vice versa)

takes 2

1

/

2

minutes.

Thermostats
The EconoMi$er IV control works with conventional thermostats

that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage
1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control

does not support space temperature sensors. Connections are
made at the thermostat terminal connection board located in the

main control box.

LED ON

LED ON

LED ON

LED ON

LED OFF

19

18

LED OFF

LED OFF

LED OFF

17

16

15

14

13

12

11

10

9

40

45

50

55

60

65

70

75

80

85

90

95 100

DEGREES FAHRENHEIT

mA

D

C

B

A

C06035

Fig. 43

--- Outside Air Temperature

Changeover Set Points

ECONOMI$ER IV

ECONOMI$ER IV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT

(FIELD-PROVIDED)

C06036

Fig. 44

--- Return Air Temperature or Enthalpy

Sensor Mounting Location

Occupancy Control
The factory default configuration for the EconoMi$er IV control

is occupied mode. Occupied mode is provided by the black
jumper from terminal TR to terminal N. When unoccupied mode

is desired, install a field-supplied timeclock function in place of
the jumper between TR and N. (See Fig. 36.) When the timeclock

contacts are closed, the EconoMi$er IV control will be in

occupied mode. When the timeclock contacts are open (removing
the 24-v signal from terminal N), the EconoMi$er IV will be in

unoccupied mode.

48H

E,

H

J

This manual is related to the following products: