beautypg.com

48h e, h j – Carrier 48HJ004---007 User Manual

Page 25

background image

25

FOR OCCUPANCY CONTROL

REPLACE JUMPER WITH

FIELD-SUPPLIED TIME CLOCK

LEGEND

DCV— Demand Controlled Ventilation

IAQ — Indoor Air Quality

LA — Low Ambient Lockout Device

OAT — Outdoor-Air Temperature

POT — Potentiometer

RAT — Return-Air Temperature

Potentiometer Defaults Settings:

Power Exhaust Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3. For field-installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT to the minimum

position.

C06028

Fig. 36

--- EconoMi$er IV Wiring

4

3

5

2

8

6

7

1

10

11

9

12

PINK

VIOLET

BLACK

BLUE

YELLOW

NOTE 1

NOTE 3

RUN

500 OHM

RESISTOR

-

+

OPTIONAL CO

SENSOR 4 - 20 mA

OUTPUT

50HJ540573

ACTUATOR

ASSEMBLY

RED

WHITE

ECONOMISER2 PLUG

DIRECT DRIVE

ACTUATOR

2

NOTES:

1. Switch on actuator must be in run position for economizer to operate.

2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077

enthalpy sensor.

3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C06029

Fig. 37

--- EconoMi$er2 with 4 to 20 mA Control Wiring

Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number

HH57AC078) is required. Replace the standard outdoor dry bulb
temperature sensor with the accessory enthalpy sensor in the same

mounting location. (See Fig. 29.) When the outdoor air enthalpy
rises above the outdoor enthalpy changeover set point, the

outdoor-air damper moves to its minimum position. The outdoor

enthalpy changeover set point is set with the outdoor enthalpy set
point potentiometer on the EconoMi$er IV controller. The set

points are A, B, C, and D. (See Fig. 45.) The factory-installed
620-ohm jumper must be in place across terminals SR and SR+

on the EconoMi$er IV controller. (See Fig. 29 and 46.)

48H

E,

H

J

This manual is related to the following products: