56

Advanced Troubleshooting

Evaporator coil is freezing

Possible Cause

Solution

Charge too low

Check sight glass

Check for leaks

Add refrigerant

TXV malfunctioning Repair or replace

High pressure switch keeps tripping

Even After Checking for Obstructions and Dirty Filters/Coils

Possible Cause

Solution

Condenser fan not operating Repair or replace

Defective switch Replace

Unit cycles on and off more than 8 times/hr

Possible Cause

Solution

Thermostat malfunctioning Check the thermostat guide for

thermostat information

Low suction pressure Check low pressure switch

Check pressure and adjust superheat

High pitched or loud rubbing noise, clanking or vibration

Possible Cause

Solution

Fans loose or malfunctioning Repair or replace

Excessive compressor vibration Replace

TXV malfunctioning Repair or replace

Replacing the blowers

NOTE: When replacing the fan or motor, replace the fan and motor as a unit.

Do not remove the motor from the impeller wheel.

IMPORTANT

This section is intended for qualified refrigeration service technicians only.

The technician should repeat all of the previous troubleshooting steps before taking action on these

more technical solutions.