Advanced Settings--
Special access
required. Contact
Wine Guardian
Service Department
for access code
Setting 8
�
Press “Mode” button to advance to Setting 8.
�
Press the “up” or “down” arrow buttons to
adjust number to the access code. Press
“Mode” button to continue onto Setting 9
through 19.
Compressor anti-
short cycling time
Setting 9
�
Press “Mode” button to advance to Setting 9.
�
Press the “Up” or “Down” arrow buttons to
adjust to the desired time in one-minute
increments. Maximum is 10 minutes,
minimum is 0 minutes.
Compressor anti-short cycling time is the
amount of allowable time between compressor
stop and restart. Rapid start/stop of compressors
can cause premature failure. Factory default is 5
minutes.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT.
Set up remote sensor
or thermostat
Setting 10
�
Press “Mode” button to advance to Setting 10.
�
Press the “Up” or “Down” arrow buttons to
adjust to the desired setting.
rS = Remote sensor
rI = Remote interface
LI= Local interface – Through-the-wall unit
only
A = Averaging – Jumper position within
sensors must be adjusted. See page 35.
Room sensor
calibration
Setting 15
�
Press “Mode” button to advance to Setting 15.
�
Press the “Up” or “Down” buttons to adjust to
the desired set point. Maximum setting is +5,
minimum setting is -5. Factory default is zero
(0). Sensor calibration setpoint changes the
actual display reading (temperature only) by
the value of this setting.
Example: Sensor reading = 55 Deg F
Setting 15 set to +4
Display reading = 59 Deg F