Vintage Cellars Wine Guardian Ducted System Manual User Manual

Page 38

background image

38

Advanced Settings--
Special access
required. Contact
Wine Guardian
Service Department
for access code

Setting 8

Press “Mode” button to advance to Setting 8.

Press the “up” or “down” arrow buttons to

adjust number to the access code. Press
“Mode” button to continue onto Setting 9

through 19.




Compressor anti-
short cycling time

Setting 9

Press “Mode” button to advance to Setting 9.

Press the “Up” or “Down” arrow buttons to

adjust to the desired time in one-minute

increments. Maximum is 10 minutes,
minimum is 0 minutes.

Compressor anti-short cycling time is the
amount of allowable time between compressor

stop and restart. Rapid start/stop of compressors
can cause premature failure. Factory default is 5

minutes.
WINE GUARDIAN DOES NOT

RECOMMEND SETTINGS LOWER THAN

FACTORY DEFAULT.

Set up remote sensor
or thermostat

Setting 10

Press “Mode” button to advance to Setting 10.

Press the “Up” or “Down” arrow buttons to

adjust to the desired setting.

rS = Remote sensor

rI = Remote interface

LI= Local interface – Through-the-wall unit
only

A = Averaging – Jumper position within
sensors must be adjusted. See page 35.




Room sensor
calibration

Setting 15

Press “Mode” button to advance to Setting 15.

Press the “Up” or “Down” buttons to adjust to

the desired set point. Maximum setting is +5,
minimum setting is -5. Factory default is zero

(0). Sensor calibration setpoint changes the
actual display reading (temperature only) by

the value of this setting.

Example: Sensor reading = 55 Deg F
Setting 15 set to +4
Display reading = 59 Deg F