Vintage Cellars Wine Guardian Ducted System Manual User Manual
Page 37

37
Deg F or Deg C
Setting 1
�
Press the “Down” arrow to change
temperature from Deg F to Deg C.
�
Press the “Up” arrow to change temperature
from Deg C to Deg F.
Low temperature
alarm setpoint
Setting 2
�
Press “Mode” button to advance to Setting 2.
�
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default
is 50 Deg. F.
High temperature
alarm setpoint
Setting 3
�
Press “Mode” button to advance to Setting 3.
�
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default
is 65 Deg F.
Low humidity alarm
set point
Setting 4
�
Press “Mode” button to advance to Setting 4.
�
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default
is 5%.
High humidity alarm
setpoint
Setting 5
�
Press “Mode” button to advance to Setting 5.
�
Press the up or down arrow buttons to adjust
to the desired setpoint. Factory default is
95%.
Add or remove
humidifier
Setting 6
�
Press “Mode” button to advance to Setting 6.
�
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default
is zero (0).
Zero (0) = No humidifier
One (1) = Stand-alone remote mounted
humidifier
Two (2) = Integral Wine Guardian mounted
humidifier
Fan AUTO or ON
Setting 7
�
Press “Mode” button to advance to Setting 7.
�
Press the “Up” or “Down” arrow buttons to
adjust number to the desired set point. Factory
default is zero (0).
Zero (0) = Auto – fan only turns on when
there is a call for cooling or heating
One (1) = Fan On – fan remains on
continuously
Settings – Press and hold the “Mode” button for five seconds to access the following settings.