Power, Battery connection, Power -4 battery connection -4 – Carrier Access Adit 3104 User Manual
Page 34

3-4
Adit 3104 - Release 1.6
Electrical Installation & Cabling
Interface Connectors
Power
The Adit 3000 is powered by a limited -48 VDC Power source. The
following options are available:
AC/DC Converter
Battery Backup module
AC/DC Converter
An AC/DC Converter generates 48VDC from any worldwide AC power source.
To connect AC power:
1. Plug power connector from AC/DC converter into rear of Adit 3000.
2. Connect AC/DC converter to wall outlet.
3. A green light should appear on the Status LED on the front of the unit.
CAUTION!
I
NCORRECT
WIRING
OF
CORD
MAY
CAUSE
EXTERNAL
FUSE
FAILURE
.
WARNING!
P
OSSIBLE
SHOCK
HAZARD
EXISTS
,
PLEASE
FOLLOW
INSTRUCTIONS
CAREFULLY
.
To connect -48 VDC power:
1. Wire appropriate connector to open end of the DC Power cable.
Orange = -48 Black = Ground (+)
2. Plug the DC power connector in the -48 VDC input power connector.
3. Apply power to connector from -48 VDC power source.
4. A green light should appear on the Status LED on the front of the unit.
WARNING!
E
XTERNAL
FUSE
PROTECTION
IS
REQUIRED
ON
THE
48VDC
INPUT
WHEN
CONNECTED
TO
A
DC
POWER
SOURCE
NOT
SUPPLIED
BY
C
ARRIER
A
CCESS
.
Fuse Recommendations, or equivalent:
Battery Connection
The Adit 3000 Battery connection is provided for Battery Backup. See Adit 3104, 3200, 3300 and 3400
Battery Backup on page 2-8 for additional information.
Recommended Fuse
AMP Rating
Littelfuse 48101.5
1.5 Amp
Bussman GMC-1.5A
1.5 Amp
PIN 10, ORANGE
PIN 5, BLACK