Tjernlund SS1R SideShot (Discontinued) with UC1 Universal Control (Version X.04) 8504117 Rev 02/04 User Manual
Page 6

5
PLENUM AND VENT HOOD CLEARANCE FROM COMBUSTIBLES
With an inlet flue gas temperature of 575oF or below, the SS1-R has been Listed for the following clearances from combustible materials:
VENT HOOD TERMINATION CLEAOR
TERMINATION CLEARANCES FOR U.S. INSTALLATIONS
Install the SS1-R according to the requirements of the National Fire Protection Association #31, #54 and #211 as follows,
(See Diagram A):
• The exit terminals of mechanical draft systems shall not be less than 7 feet above grade when located adjacent to public walk
ways.
• A venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.
• The venting system shall terminate at least 4 feet below, 4 feet horizontally from or 1 foot above any door, window or gravity air
inlet into any building.
• The bottom of the vent terminal shall be located at least 12 inches above grade.
• Arrange the exit terminal so that the flue gases are not directed so as to jeopardize people, overheat combustible structures or
enter buildings.
• Not to be less than 2 feet from an adjacent building.
The SS1-R is also Listed to terminate a minimum of 12" below, above or horizontally from a soffit, deck or adjacent sidewall.
Pre-Purge
Post-Purge
Pre-Cycle
Prover Status
Check Deactivated
DIP SWITCH NUMBERING
1
ON
2
3 4 5 6 7 8
9
ON
PRE-PURGE SETTINGS (SEE “PRE-PURGE”, ON PAGE 4 PRIOR TO SETTING)
1 2
1 2
1 2
1 2
0 Seconds
5 Seconds
20 Seconds
35 Seconds
ON
POST-PURGE SETTINGS (SEE “POST-PURGE”, ON PAGE 4 PRIOR TO SETTING)
ON
4
3
4
8
6
5
7
3
5 6 7 8
3 4 5 6 7 8
3
7
5
4
6
8
4
3
4
8
6
5
7
3
5 6 7 8
3 4 5 6 7 8
4 Minutes
8 Minutes
16 Minutes
1 Minute
0 Seconds
30 Seconds
2 Minutes
IMPORTANT
Vent Hood and top of Plenum: Zero Clearance
Plenum front and sides: 1/2 inch
Plenum rear: 3 inches
P1 & P2 PRE-CYCLE FAN PROVER STATUS CHECK
The Pre-Cycle Prover Status Check is deactivated from the factory on the SS1-R. Because of the
low set point of the SS1-R Fan Prover (as low as .03" w.c.) cross winds may cause the Fan Prover
to close prior to a call for heat. Activating the Prover Status Check on the SS1-R may cause
nuisance lockouts.
Pre-Cycle
Prover Status
Check Deactivated
9
1 9
LED 1 AMBER
LED 2 GREEN
LED 3 GREEN
LED 4 RED
LED 5 RED
ON