Tjernlund CIC1 Heater Interlock Control for COP2 8504209 User Manual
Uc1 to cop2 wiring, Tjernlund products, inc, Warning
CIC1 OPERATION & WIRING CONNECTIONS
The CIC1 is the standard interlock control for use with Tjernlund's COP2 Constant Operating Pressure Control. It incorporates a UC1
burner interlock control with an isolation relay used to close the C1 and C2 actuation contacts of the COP2 Controller. This instruction
covers the interface of a UC1 burner interlock control with a COP2 constant operating pressure controller.
IMPORTANT: Follow all
cautions, warnings and burner interlock directions within the UC1 instructions.
1. Install the included activation isolation relay in the square knock-out located on top of the COP2 electrical box.
2. Wire the Black (MTR) and White (N) leads from the UC1 whip to the Black and White leads of the activation isolation relay.
3. Remove female quick connect terminals on Blue and Yellow leads from UC1 cable whip. Connect the Blue (P1) and Yellow (P2)
leads from the UC1 whip to P1 and P2 of the COP2 terminal strip.
4. Connect the (2) gray leads of the activation isolation relay to C1 and C2 of the COP2 terminal strip.
Unconnected or insecure ground connections will cause improper system operation. Verify that all grounding locations are securely and
properly grounded to earth.
SAFETY INTERLOCK TEST
After the installation is completed, including all wiring connections perform the following interlock test: Allow for a call for heat. Verify that
the exhaust fan is operating prior to the blue LED on the UC1 circuit board being illuminated. Once the blue LED is lit pull the insulated
connector from terminal P1 of the UC1 circuit board off and verify that 10 seconds later that burner operation is disrupted. If not correct
any wiring errors and repeat interlock test. Call 800-255-4208 for assistance.
Copyright © 2014, Tjernlund Products, Inc. All rights reserved.
P/N 8504209
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
FIGURE 8052083 6-11-14
GRY
GRY
VIO
YEL
RED
V+
COM
1-10
P2
P1
C2
C1
GRN
GRN
LED
POWER
RED
DRY
24V
115V
RELAY
MTR
NO
INC.
9183006
TJERNLUND
PRODUCTS,
R
XL
K2
MOTOR
COM
M
N
XN
NO
K1
INTERLOCK
RELAY
J1
COM
J2
JUMPER
CALL
GND
F
C
P1
P2
3
5
4
2
1
UC1 TO COP2 WIRING
= LOW VOLTAGE
= 115 VAC
LEGEND
UC1 CONTROL
COP2 BOX
YELLOW
BLUE
GREEN
GRAY
GRAY
WHITE
BLACK
WHITE
BLACK
UC1 CABLE
7 8
LED'S
6
6
4
BLUE
YELLOW
GREEN
BLACK
WHITE
WARNING
The burner interlock feature is not activated unless jumper(s) is installed
as depicted in OPTION 3 or 4 of the COP2 wiring diagram. Failure to add
jumper(s) will result in unsafe operation of the COP2 Control.
Do not use
Option 1 or 2.
OPTION 3: Exhaust with CIC1 Interlock
OPTION 4: Exhaust with CIC1 Interlock, No Overdraft Fault
Refer to COP2 Wiring diagram in COP2 instructions for complete diagram.
1
2
3
4
5
6
7
8
FRONT VIEW
TOP VIEW
Z B A
GND
3.3V
Z B A
GND
3.3V
Z B A
GND
3.3V
OPTION 1
OPTION 2
OPTION 3
OFF
ON
DIP SWITCHES
OUT = ON, IN = OFF
Z B A
GND
3.3V
OPTION 4
TB6
COP2 CIRCUIT BOARD INTERFACE OPTIONS