CIC1 OPERATION & WIRING CONNECTIONS

The CIC1 is the standard interlock control for use with Tjernlund's COP2 Constant Operating Pressure Control. It incorporates a UC1
burner interlock control with an isolation relay used to close the C1 and C2 actuation contacts of the COP2 Controller. This instruction
covers the interface of a UC1 burner interlock control with a COP2 constant operating pressure controller.

IMPORTANT: Follow all

cautions, warnings and burner interlock directions within the UC1 instructions.

1. Install the included activation isolation relay in the square knock-out located on top of the COP2 electrical box.

2. Wire the Black (MTR) and White (N) leads from the UC1 whip to the Black and White leads of the activation isolation relay.

3. Remove female quick connect terminals on Blue and Yellow leads from UC1 cable whip. Connect the Blue (P1) and Yellow (P2)

leads from the UC1 whip to P1 and P2 of the COP2 terminal strip.

4. Connect the (2) gray leads of the activation isolation relay to C1 and C2 of the COP2 terminal strip.

Unconnected or insecure ground connections will cause improper system operation. Verify that all grounding locations are securely and
properly grounded to earth.

SAFETY INTERLOCK TEST

After the installation is completed, including all wiring connections perform the following interlock test: Allow for a call for heat. Verify that
the exhaust fan is operating prior to the blue LED on the UC1 circuit board being illuminated. Once the blue LED is lit pull the insulated
connector from terminal P1 of the UC1 circuit board off and verify that 10 seconds later that burner operation is disrupted. If not correct
any wiring errors and repeat interlock test. Call 800-255-4208 for assistance.

Copyright © 2014, Tjernlund Products, Inc. All rights reserved.

P/N 8504209

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

FIGURE 8052083 6-11-14

GRY

GRY

VIO

YEL

RED

V+

COM

1-10

P2

P1

C2

C1

GRN

GRN

LED

POWER

RED

DRY

24V

115V

RELAY

MTR

NO

INC.

9183006

TJERNLUND

PRODUCTS,

R

XL

K2

MOTOR

COM

M

N

XN

NO

K1

INTERLOCK

RELAY

J1

COM

J2

JUMPER

CALL

GND

F

C

P1

P2

3

5

4

2

1

UC1 TO COP2 WIRING

= LOW VOLTAGE
= 115 VAC

LEGEND

UC1 CONTROL

COP2 BOX

YELLOW

BLUE

GREEN

GRAY

GRAY

WHITE

BLACK

WHITE

BLACK

UC1 CABLE

7 8

LED'S

6

6

4

BLUE

YELLOW

GREEN

BLACK

WHITE

WARNING

The burner interlock feature is not activated unless jumper(s) is installed
as depicted in OPTION 3 or 4 of the COP2 wiring diagram. Failure to add
jumper(s) will result in unsafe operation of the COP2 Control.

Do not use

Option 1 or 2.

OPTION 3: Exhaust with CIC1 Interlock

OPTION 4: Exhaust with CIC1 Interlock, No Overdraft Fault

Refer to COP2 Wiring diagram in COP2 instructions for complete diagram.

1

2

3

4

5

6

7

8

FRONT VIEW

TOP VIEW

Z B A

GND

3.3V

Z B A

GND

3.3V

Z B A

GND

3.3V

OPTION 1

OPTION 2

OPTION 3

OFF

ON

DIP SWITCHES

OUT = ON, IN = OFF

Z B A

GND

3.3V

OPTION 4

TB6

COP2 CIRCUIT BOARD INTERFACE OPTIONS