Rice Lake 920i Programmable HMI Indicator/Controller - ControlNet Interface User Manual
Page 17

Appendix
13
Param3 =
0, $ first field shall equal 0
,, $ path size,path
0x0000, $ descriptor
199, $ data type : 16-bit Unsigned Integer
2, $ data size in bytes
"Input Size", $ name
"", $ units
"", $ help string
4,454,20, $ min,max,default data values
0,0,0,0, $ mult,dev,base,offset scaling not used
0,0,0,0, $ mult,dev,base,offset link not used
0;
[Connection Manager]
Connection1 =
0x04010002, $ trigger & transport
$ 0-15 = supported transport classes (class 1)
$ 16 = cyclic (1 = supported)
$ 17 = change of state (0 = not supported)
$ 18 = on demand (0 = not supported)
$ 19-23 = reserved (must be zero)
$ 24-27 = exclusive owner
$ 28-30 = reserved (must be zero)
$ 31 = client 0 (don't care for classes 0 and 1)
0x44240405, $ point/multicast & priority & realtime format
$ 0 = O=>T fixed (1 = supported)
$ 1 = O=>T variable (0 = not supported)
$ 2 = T=>O fixed (1 = supported)
$ 3 = T=>O variable (0 = not supported)
$ 4-7 = reserved (must be zero)
$ 8-10 = O=>T header (4 byte run/idle)
$ 11 = reserved (must be zero)
$ 12-14 = T=>O header
$ 15 = reserved (must be zero)
$ 16-19 = O=>T point-to-point
$ 20-23 = T=>O multicast
$ 24-27 = O=>T scheduled
$ 28-31 = T=>O scheduled
,Param2,, $ O=>T RPI,Size,Format
,Param3,, $ T=>O RPI,Size,Format
,, $ config part 1 (dynamic assemblies)
,, $ config part 2 (module configuration)
"Discrete Exclusive Owner", $ connection name
"", $ Help string
"20 04 24 01 2C 96 2C 64"; $ exclusive output path
1_PLC5C_RTD_Format1 = 1_PLC5C_1794_Discrete_RTD_Format;