Operating parameters, Liquid phase storage – Taylor-Wharton KRYOS Controller User Manual
Page 12

10
KRYOS
Comm Port
(RS-232)
Remote
Alarm
Remote Alarm:
Normal Condition............. Continuity Between pins 2 and 3
Alarm Condition................. Continuity Between pins 1 and 2
Sensor
24 VAC
Power
Solenoid
Temp 1
(Receptacle
View)
Temp 2
3
1 - Purple Wire: Normally Closed
2 - Orange Wire: Normally Open
3 - Grey Wire: Normally Open
2 1
Figure 5.0 Remote Alarm Plug Connection
Operating Parameters
When materials are immersed in liquid nitrogen, they will assume the temperature
of the liquid (-196°C/-320°F). When material is stored in the vapor phase over the
liquid, the liquid nitrogen is still a very cold refrigerant, but the refrigerator’s interior
temperature increases somewhat as product is stored higher over the liquid. This
temperature differential is not significant in many biological storage applications,
and is affected by the amount of product stored in the refrigerator, the type and size
of inventory control system, and the liquid level in the unit.
The liquid level in the refrigerator is determined by the position of the of the
Thermistor Assembly in the sensor tube. These sensors are set at installation to
maintain a specific liquid level. A filling cycle is initiated when the level falls below
the Start Fill sensor and is completed when the Stop Fill sensor is reached. This
filling cycle repeats when the level fall below the Start Fill sensor. Sensor Probe
assignments may be changed on the controller keypad to define new start and stop
levels, and these levels may be set independently to vary the liquid level differential
between fills. Prior to the initial fill of the refrigerator, a determination should be
made whether vapor phase or liquid phase storage will be utilized.
All units are supplied with a seven thermistor assembly and a freeze-guard sensor
unless otherwise specified. Factory setting positions for the K-Series are Start Fill 3 in.
(76.2 mm) and Stop position 6 in. (152.4 mm). The LABS factory setting positions
will maintain liquid level within a distance of 2 in. (50.8 mm) from the bottom of the
operating tray on the LABS 20K, 38K, 40K, 80K units, and 3 in. (76.2 mm) from the
bottom of the operating tray on the LABS 94K.
Liquid Phase Storage
Liquid phase storage is normally utilized when liquid nitrogen temperatures are
required to maintain stored product viability and the storage medium is adequate
for storage in liquid nitrogen.
In a typical liquid phase storage system, the liquid level sensors are positioned to
maintain the liquid level at or below the top level of the inventory control system.
During operation, the upper levels of the inventory control system will at times
become exposed as the liquid level fluctuates.
Care must be taken to ensure that the liquid level remains below the bottom of the
refrigerator lid. Exposure to liquid nitrogen may result in physical damage to the lid.
Additionally, operating the refrigerator with high liquid levels characteristic of liquid
phase storage may result in turbulence during fill cycles. Caution must be exercised
if the refrigerator lid is opened during a fill, and appropriate safety equipment
should always be worn.
10
KRYOS
Comm Port
(RS-232)
Remote
Alarm
Remote Alarm:
Normal Condition............. Continuity Between pins 2 and 3
Alarm Condition................. Continuity Between pins 1 and 2
Sensor
24 VAC
Power
Solenoid
Temp 1
(Receptacle
View)
Temp 2
3
1 - Purple Wire: Normally Closed
2 - Orange Wire: Normally Open
3 - Grey Wire: Normally Open
2 1
Figure 5.0 Remote Alarm Plug Connection
Operating Parameters
When materials are immersed in liquid nitrogen, they will assume the temperature
of the liquid (-196°C/-320°F). When material is stored in the vapor phase over the
liquid, the liquid nitrogen is still a very cold refrigerant, but the refrigerator’s interior
temperature increases somewhat as product is stored higher over the liquid. This
temperature differential is not significant in many biological storage applications,
and is affected by the amount of product stored in the refrigerator, the type and size
of inventory control system, and the liquid level in the unit.
The liquid level in the refrigerator is determined by the position of the of the
Thermistor Assembly in the sensor tube. These sensors are set at installation to
maintain a specific liquid level. A filling cycle is initiated when the level falls below
the Start Fill sensor and is completed when the Stop Fill sensor is reached. This
filling cycle repeats when the level fall below the Start Fill sensor. Sensor Probe
assignments may be changed on the controller keypad to define new start and stop
levels, and these levels may be set independently to vary the liquid level differential
between fills. Prior to the initial fill of the refrigerator, a determination should be
made whether vapor phase or liquid phase storage will be utilized.
All units are supplied with a seven thermistor assembly and a freeze-guard sensor
unless otherwise specified. Factory setting positions for the K-Series are Start Fill 3 in.
(76.2 mm) and Stop position 6 in. (152.4 mm). The LABS factory setting positions
will maintain liquid level within a distance of 2 in. (50.8 mm) from the bottom of the
operating tray on the LABS 20K, 38K, 40K, 80K units, and 3 in. (76.2 mm) from the
bottom of the operating tray on the LABS 94K.
Liquid Phase Storage
Liquid phase storage is normally utilized when liquid nitrogen temperatures are
required to maintain stored product viability and the storage medium is adequate
for storage in liquid nitrogen.
In a typical liquid phase storage system, the liquid level sensors are positioned to
maintain the liquid level at or below the top level of the inventory control system.
During operation, the upper levels of the inventory control system will at times
become exposed as the liquid level fluctuates.
Care must be taken to ensure that the liquid level remains below the bottom of the
refrigerator lid. Exposure to liquid nitrogen may result in physical damage to the lid.
Additionally, operating the refrigerator with high liquid levels characteristic of liquid
phase storage may result in turbulence during fill cycles. Caution must be exercised
if the refrigerator lid is opened during a fill, and appropriate safety equipment
should always be worn.
10
KRYOS
Comm Port
(RS-232)
Remote
Alarm
Remote Alarm:
Normal Condition............. Continuity Between pins 2 and 3
Alarm Condition................. Continuity Between pins 1 and 2
Sensor
24 VAC
Power
Solenoid
Temp 1
(Receptacle
View)
Temp 2
3
1 - Purple Wire: Normally Closed
2 - Orange Wire: Normally Open
3 - Grey Wire: Normally Open
2 1
Figure 5.0 Remote Alarm Plug Connection
Operating Parameters
When materials are immersed in liquid nitrogen, they will assume the temperature
of the liquid (-196°C/-320°F). When material is stored in the vapor phase over the
liquid, the liquid nitrogen is still a very cold refrigerant, but the refrigerator’s interior
temperature increases somewhat as product is stored higher over the liquid. This
temperature differential is not significant in many biological storage applications,
and is affected by the amount of product stored in the refrigerator, the type and size
of inventory control system, and the liquid level in the unit.
The liquid level in the refrigerator is determined by the position of the of the
Thermistor Assembly in the sensor tube. These sensors are set at installation to
maintain a specific liquid level. A filling cycle is initiated when the level falls below
the Start Fill sensor and is completed when the Stop Fill sensor is reached. This
filling cycle repeats when the level fall below the Start Fill sensor. Sensor Probe
assignments may be changed on the controller keypad to define new start and stop
levels, and these levels may be set independently to vary the liquid level differential
between fills. Prior to the initial fill of the refrigerator, a determination should be
made whether vapor phase or liquid phase storage will be utilized.
All units are supplied with a seven thermistor assembly and a freeze-guard sensor
unless otherwise specified. Factory setting positions for the K-Series are Start Fill 3 in.
(76.2 mm) and Stop position 6 in. (152.4 mm). The LABS factory setting positions
will maintain liquid level within a distance of 2 in. (50.8 mm) from the bottom of the
operating tray on the LABS 20K, 38K, 40K, 80K units, and 3 in. (76.2 mm) from the
bottom of the operating tray on the LABS 94K.
Liquid Phase Storage
Liquid phase storage is normally utilized when liquid nitrogen temperatures are
required to maintain stored product viability and the storage medium is adequate
for storage in liquid nitrogen.
In a typical liquid phase storage system, the liquid level sensors are positioned to
maintain the liquid level at or below the top level of the inventory control system.
During operation, the upper levels of the inventory control system will at times
become exposed as the liquid level fluctuates.
Care must be taken to ensure that the liquid level remains below the bottom of the
refrigerator lid. Exposure to liquid nitrogen may result in physical damage to the lid.
Additionally, operating the refrigerator with high liquid levels characteristic of liquid
phase storage may result in turbulence during fill cycles. Caution must be exercised
if the refrigerator lid is opened during a fill, and appropriate safety equipment
should always be worn.