beautypg.com

Warning, Operation instructions, Maintenance instructions – Qmark MEDH - Portable Electric Blower Heaters User Manual

Page 3: Thermostat, Cord preparation for portable heaters, Figure 2, Diag. 1 – factory wired 3 phase, Diag. 1a – field conversion to 1 phase, Diag. 2a – field conversion to 1 phase, Diag. 2 – factory wired 3 phase

background image

3

OPERATION INSTRUCTIONS

THERMOSTAT

Heaters include a bimetal thermostat for the automatic control
of the exiting air temperature. The thermostat knob controls the heating
elements and fan functions. The heater and fan are
de-energized with the knob in the extreme clockwise position.
Turning the knob clockwise from the off position to the fan
position will energize the fan only, for use in summer cooling.
The adjustment knob controls power to the heater and fan
when turned further in the clockwise direction, with the highest tempera-
ture setting in the extreme clockwise position.
The temperature setting in the heater mode is approximately
40°F in the low setting and 100°F at the highest setting.
Note: The adjustment knob should be turned to the fan only
setting after use for heating. The fan should be left on for at least 3 min-
utes to remove residual heat from the unit and to prevent overheating of
the housing.

Cord Preparation for Portable Heaters

1. Determine the gage and number of conductors fromChart A using

amps and phase from the heater nameplate. It is not recommended
that cord exceed 50 feet in length.

2. Strip off outer jacket of cord and insulation from lead wires. The tabu-

lation below provides the strip dimensions for the
various Chromalox portable heaters. See the nameplate on the heater
for the Model number.

3. Slide fitting onto cord and tighten knurled nut to secure fitting

to cord.

4. Select plug to match electrical rating of cord.
5. On opposite end of cord prepare end as directed by

instructions that are provided with the plug.

6. Attach cord assembly to heater as shown in Fig. 2 below:

Model No.

A

B

C

All Models

8”

1”

0.5”

Figure 2

Run wire tie through slots in bracket and over cord.
Pull tab of wire tie to provide cord strain relief.

Power
wires

Ground
wire

90° fitting

"A"

"B" (Insulation strip dimension for ground wire).

"C" (Insulation strip dimension for power wires).

T3
T2
T1

L3
L2
L1

2

1

3

Thermostat

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

Red

Motor

Blu

Blk

Wht

Cutout

6

4

Diag. 1 – FACTORY WIRED 3 PHASE

T2
T1

L2
L1

2

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

All control wiring

same as Diag. 1

Instructions:
1. Loosen screws on load side of contactor. Remove all lead wire.
2. Insert lead wires numbers 1, 3, and 5 into box lug connector "T1". Tighten screws
on box lug connector.
3. Insert lead wires numbers 2, 4, and 6 into box lug connector "T2". Tighten screws
on box lug connector.
4. Examine wiring to make certain it is per above diagram.

Diag. 1a – FIELD CONVERSION TO 1 PHASE

All control wiring

same as Diag. 2

T2
T1

L2
L1

2

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

All even numbered wires to T2

All odd numbered wires to T1

Contactor

Instructions:
1. Loosen screws on load side of contactor. Remove all lead wire.
2. Insert lead wires numbers 1, 3, and 5 into box lug connector "T1".
Tighten screws on box lug connector.
3. Insert lead wires numbers 2, 4, and 6 into box lug connector "T2".
Tighten screws on box lug connector.
4. Examine wiring to make certain it is per above diagram.

Diag. 2a – FIELD CONVERSION TO 1 PHASE

T3
T2
T1

L3
L2
L1

2

1

3

Thermostat

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

Blk/Red or Grey

Motor

Blk

Wht

Cutout

6

4

Contactor

1

3

5

2

4

6

To T3

To T3

To T1

To T2

To T1

To T2

Fan Relay

A2

T2

T1

A1

L2

L1

XFMR

Blk

Black

White

Diag. 2 – FACTORY WIRED 3 PHASE

T3
T2
T1

L3
L2
L1

11

1

3

Thermostat

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

9

10

7

8

12

Front of
Heater

10

9

4

3

2

1

Motor

Blue

Cutout

6

4

Contactor

1

3

5

2

4

6

To T3

To T3

To T1

To T2

To T1

To T2

Red

Black

White

6

5

12

11

8

7

Diag. 3 – FACTORY WIRED 3 PHASE

MAINTENANCE INSTRUCTIONS

Replace or repair damaged cords or plugs immediately. Check
tightness of all electrical connections prior to energizing the
heater. Blow out or vacuum away any dirt or debries that may
have accumulated around the control enclosure fan motor or
heating elements.

Electric Shock Hazard. Disconnect heater from power supply
before servicing and/or inspecting the heater; failure to do so
may result in electrical shock.

a

WARNING

!