INSTALLATION

The heaters may be mounted at any convenient height above

floor. The minimum spacings, shown in Figure 4, should be main-

tained to adjacent walls and ceiling. If floor heat is desired, do not

mount higher than 8’ to 10’ above floor.

Controlling thermostats to individual heaters should be mount-

ed at shoulder height on inside walls or columns and clear of the

discharge air stream of the unit. Allow at least 4’ in front of heater

for air stream to discharge freely. Do not mount mercury type ther-

mostat directly on units, vibration could cause malfunction.

Heater may be mounted on a shelf or stand from the bottom. Be

sure the mounting clearances are maintained and that bottom of

unit has at least 1’ clearance underneath it. This is necessary for

good air circulation and servicing of heat exchanger. All mounting

methods must allow for removal of front cover.

The mounting and anchoring provisions must take into account

the unit vibration and cantilevered loading when wall or pole

mounted. One of the mounting kits, shown in Figure 5, 6 and 7,

must be used whenever possible.