Table 1D — 40RUS Physical Data, SI — Chilled Water Units

LEGEND

UNIT 40RUS*

25

28

30

NOMINAL CAPACITY (kW)

70

87

105

OPERATING WEIGHT (kg)

Base Unit

310

469

473

Plenum

102

148

148

FANS

Qty...Diam. (mm)

2...381

2...457

2...457

Nominal Airflow (L/s)

3775

4719

5663

Airflow Range (L/s)

2831 – 4719

3539 – 5899

4247 – 7079

Nominal Motor kW (Standard Motor)

208/230-3-60 and 460-3-60

3.73

5.60

7.46

575-3-60

3.73

5.60

7.46

Motor Speed (r/s)

208/230-3-60 and 460-3-60

29.1

29.1

29.1

575-3-60

29.1

29.3

29.3

CHILLED WATER COIL

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

Max Working Pressure (kPag)

2999

Face Area (sq m) – Upper

1.02

1.15

1.44

Face Area (sq m) – Lower

0.77

1.15

1.15

Rows...Fins/m

3...591

3...591

3...591

PIPING CONNECTIONS,

Quantity...Size (in.)

Chilled Water — In

2...1

3

/

8

ODM

2...2

1

/

8

ODM

2...2

1

/

8

ODM

Chilled Water — Out

2...1

3

/

8

ODM

2...2

1

/

8

ODM

2...2

1

/

8

ODM

Steam Coil, In (MPT)

1...2

1

/

2

Steam Coil, Out (MPT)

1...1

1

/

2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...1

1

/

4

ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (mm.)

4...406 x 508 x 51
4...406 x 610 x 51

4...508 x 610 x 51
4...508 x 635 x 51

Access Location

Either Side

STEAM COIL

Max Working Pressure (kPag at 125°C)

138

Total Face Area (sq m)

1.24

1.39

1.39

Rows...Fins/m

1...394

1...394

1...394

HOT WATER COIL

Max Working Pressure (kPag)

1034

Total Face Area (sq m)

1.24

1.39

1.39

Rows...Fins/m

2...335

2..493

2...493

Water Volume

(L)

52.6

54.1

(m

3

)

0.052

0.054

Field installed accessory only.