beautypg.com

Carrier REFRIGERANT R-410A User Manual

Page 7

background image

7

Table 1C — 40RUS Physical Data, English — Chilled Water Units

LEGEND

UNIT 40RUS*

25

28

30

NOMINAL CAPACITY (Tons)

20

25

30

OPERATING WEIGHT (lb)

Base Unit

683

1035

1042

Plenum

225

325

325

FANS

Qty...Diam. (in.)

2...15

2...18

2...18

Nominal Airflow (cfm)

8,000

10,000

12,000

Airflow Range (cfm)

6,000 – 10,000

7,500 – 12,500

9,000 – 15,000

Nominal Motor Hp (Standard Motor)

208/230-3-60 and 460-3-60

5.0

7.5

10.0

575-3-60

5.0

7.5

10.0

Motor Speed (rpm)

208/230-3-60 and 460-3-60

1745

1745

1745

575-3-60

1745

1755

1755

CHILLED WATER COIL

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

Max Working Pressure (psig)

435

Face Area (sq ft) – Upper

11.0

12.4

15.5

Face Area (sq ft) – Lower

8.3

12.4

12.4

Rows...Fins/in.

3...15

PIPING CONNECTIONS,

Quantity...Size (in.)

Chilled Water — In

2...1

3

/

8

ODM

2...2

1

/

8

ODM

2...2

1

/

8

ODM

Chilled Water — Out

2...1

3

/

8

ODM

2...2

1

/

8

ODM

2...2

1

/

8

ODM

Steam Coil, In (MPT)

1...2

1

/

2

Steam Coil, Out (MPT)

1...1

1

/

2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...1

1

/

4

ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2
4...16 x 24 x 2

4...20 x 24 x 2
4...20 x 25 x 2

Access Location

Either Side

STEAM COIL

Max Working Pressure (psig at 260°F)

20

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

1...10

1...10

1...10

HOT WATER COIL

Max Working Pressure (psig)

150

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

2...8.5

2...12.5

2...12.5

Water Volume

(gal)

13.9

14.3

(ft

3

)

1.1

1.90

Field installed accessory only.