beautypg.com

Carrier REFRIGERANT R-410A User Manual

Page 13

background image

13

Table 2 — Factory-Installed Nozzle and Distributor Data

Table 3 — Fitting Requirements

UNIT

COIL TYPE

STD

TXV

Qty...Part No.

DISTRIBUTOR

Qty...Part No.

FEEDER TUBES

PER DISTRIBUTOR

Qty...Size (in.)

NOZZLE

Qty...Part No.

40RU*25

4 Row

2...BBIZE-8-GA

2...1135

18...

3

/

16

2...G6

40RU*28

4 Row

2...BBIZE-15-GA

2...1126

20...

3

/

16

2...C15

40RU*30

4 Row

2...BBIZE-15-GA

2...1126

24...

3

/

16

2...C17

Feeder tube size is

1

/

4

in. (6.35 mm).

NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

UNIT

ACCESS

HOLE NO.

CONNECTION

TYPE

CIRCUIT

FITTINGS REQUIRED

(in.)

40RUA25

1

Suction

Lower

1

1

/

8

Street Elbow

1

1

/

8

Nipple, 7

5

/

8

L

1

1

/

8

Long Radius Elbow

2

Liquid

Lower

5

/

8

Street Elbow

5

/

8

Nipple, 6

1

/

2

L

5

/

8

Long Radius Elbow

3

Liquid

Upper

5

/

8

Street Elbow

5

/

8

Nipple, 9

1

/

2

L

5

/

8

Long Radius Elbow

4

Suction

Upper

1

1

/

8

Nipple, 5

5

/

8

L

1

1

/

8

Long Radius Elbow

1

1

/

8

Nipple, 11 L

1

1

/

8

Long Radius Elbow

40RUS25

4

Supply

Lower

1

3

/

8

Long Radius Elbow

1

3

/

8

Nipple, 3

3

/

4

L

1

3

/

8

Long Radius Elbow

5

Return

Lower

1

3

/

8

Long Radius Elbow

1

3

/

8

Nipple, 3

3

/

8

L

1

3

/

8

Long Radius Elbow

6

Return

Upper

1

3

/

8

Long Radius Elbow

1

3

/

8

Nipple, 7 L

1

3

/

8

Long Radius Elbow

7

Supply

Upper

1

3

/

8

Long Radius Elbow

1

3

/

8

Nipple, 11

3

/

4

L

1

3

/

8

Long Radius Elbow