Carrier REFRIGERANT R-410A User Manual

Page 5

background image

5

Table 1A — 40RUA Physical Data, English — Cooling Units

LEGEND

UNIT 40RUA*

25

28

30

NOMINAL CAPACITY (Tons)

20

25

30

OPERATING WEIGHT (lb)

Base Unit with TXV

730

1050

1062

Plenum

225

325

325

FANS

Qty...Diam. (in.)

2...15

2...18

2...18

Nominal Airflow (cfm)

8,000

10,000

12,000

Airflow Range (cfm)

6,000 – 10,000

7,500 – 12,500

9,000 – 15,000

Nominal Motor Hp (Standard Motor)

208/230-3-60 and 460-3-60

5.0

7.5

10.0

575-3-60

5.0

7.5

10.0

Motor Speed (rpm)

208/230-3-60 and 460-3-60

1745

1745

1745

575-3-60

1745

1755

1755

REFRIGERANT

R-410A

Operating charge (lb)
(approx per circuit)

3.5

4.5

5.0

DIRECT-EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

Max Working Pressure (psig)

450

Face Area (sq ft)

19.88

24.86

29.83

No. of Splits

2

2

2

No. of Circuits per Split

18

20

24

Split Type...Percentage

Face...50/50

Fins/in.

17

15

15

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF)

2...1

1

/

8

2...1

3

/

8

2...1

3

/

8

DX Coil — Liquid Refrigerant (ODF)

2...

5

/

8

Steam Coil, In (MPT)

1...2

1

/

2

Steam Coil, Out (MPT)

1...

1

/

2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...1

1

/

4

ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2
4...16 x 24 x 2

4...20 x 24 x 2
4...20 x 25 x 2

Access Location

Either Side

STEAM COIL

Max Working Pressure (psig at 260°F)

20

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

1...10

1...10

1...10

HOT WATER COIL

Max Working Pressure (psig)

150

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

2...8.5

2...12.5

2...12.5

Water Volume

(gal)

13.9

14.3

(ft

3

)

1.85

1.90

DX

Direct Expansion

TXV

Thermostatic Expansion Valve

Units are shipped without refrigerant charge.

Field installed accessory only.