Table 1B — 40RUA Physical Data, SI — Cooling Units

LEGEND

UNIT 40RUA*

25

28

30

NOMINAL CAPACITY (kW)

70

87

105

OPERATING WEIGHT (kg)

Base Unit with TXV

331

477

482

Plenum

102

148

148

FANS

Qty...Diam. (mm)

2...381

2...457

2...457

Nominal Airflow (L/s)

3775

4119

5663

Airflow Range (L/s)

2831 – 4719

3539 – 5899

4247 – 7079

Nominal Motor kW (Standard Motor)

208/230-3-60 and 460-3-60

3.73

5.60

7.46

575-3-60

3.73

5.60

7.46

Motor Speed (r/s)

208/230-3-60 and 460-3-60

29.1

29.1

29.1

575-3-60

29.1

29.3

29.3

REFRIGERANT

R-410A

Operating charge (kg)
(approx per circuit)

1.59

2.04

2.27

DIRECT-EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

Max Working Pressure (kPag)

3102

Face Area (sq m)

1.85

2.30

2.77

No. of Splits

2

2

2

No. of Circuits per Split

18

20

24

Split Type...Percentage

Face...50/50

Fins/m

670

591

591

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF)

2...1

1

/

8

2...1

3

/

8

2...1

3

/

8

DX Coil — Liquid Refrigerant (ODF)

2...

5

/

8

Steam Coil, In (MPT)

1...2

1

/

2

Steam Coil, Out (MPT)

1...

1

/

2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...1

1

/

4

ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (mm.)

4...406 x 508 x 51
4...406 x 610 x 51

4...508 x 610 x 51
4...508 x 635 x 51

Access Location

Either Side

STEAM COIL

Max Working Pressure (kPag at 126°C)

138

Total Face Area (sq m)

1.24

1.39

1.39

Rows...Fins/m

1...394

1...394

1...394

HOT WATER COIL

Max Working Pressure (kPag)

1034

Total Face Area (sq m)

1.24

1.39

1.39

Rows...Fins/m

2...335

2...335

2...335

Water Volume

(L)

52.6

54.1

(m

3

)

0.052

0.054

DX

Direct Expansion

TXV

Thermostatic Expansion Valve

Units are shipped without refrigerant charge.

Field installed accessory only.