Table 6—electrical data, Table 7—setup switch description – Carrier DOWNFLOW HORIZONTAL 2-SPEED User Manual
Page 11
This furnace can be installed with either single-stage heating or
2-stage heating thermostat.
For single-stage thermostats, connect thermostat W to W/W1 at
furnace control terminal block. (See Fig. 15.) For single-stage
thermostats the control determines, based on length of previous
heating on and off cycles, when to operate in low- and high-gas
heat for optimum comfort. Setup Switch-2 (SW-2) must be in the
factory-shipped OFF position. See Fig. 17 and Tables 6 and 7 for
setup switch information.
If 2-stage heating thermostat is to be used, move SW-2 to ON
position at end of furnace installation. This overrides built-in
control process for selecting high and low stage and allows 2-stage
thermostat to select gas heating modes. The W2 from thermostat
must be connected to W2 on control terminal block. (See Fig. 16.)
Before operating furnace, check each manual reset switch for
continuity. If necessary, press and release button to reset switch.
Table 6—Electrical Data
UNIT
SIZE
VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
MAX
UNIT
AMPS
MIN
WIRE
GAGE
MAX WIRE
LENGTH
FT‡
MAX FUSE OR
HACR-TYPE
CKT BKR AMPS†
Max*
Min*
065-08
115—60—1
127
104
8.0
14
46
15
065-12
115—60—1
127
104
10.5
14
35
15
085-12
115—60—1
127
104
12.0
14
30
15
085-16
115—60—1
127
104
14.2
14
26
15
105-16
115-60-1
127
104
13.2
14
29
15
105-20
115—60—1
127
104
17.2
12
33
20
125-20
115—60—1
127
104
17.9
12
32
20
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Time-delay fuse is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
→ Fig. 15—Heating and Cooling Application Wiring Diagram With 1-Stage Thermostat and Condensing Unit
A97443
115-V FUSED
DISCONNECT
SWITCH
(WHEN REQUIRED)
JUNCTION
BOX
CONTROL
BOX
24-V
TERMINAL
BLOCK
TWO-WIRE
HEATING-
ONLY
FIVE
WIRE
1-STAGE THERMOSTAT TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
CONDENSING
UNIT
FURNACE
COM
R
W
Y
R
G
C
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
WHT
BLK
WHT
BLK
W/W1
W2
Y/Y2
G
NOTES:
1. Connect Y-terminal as shown for proper operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced,
use same type or equivalent wire.
Table 7—Setup Switch Description
SETUP
SWITCH NO.
NORMAL
POSITION
DESCRIPTION OF USE
SW-1
Only High-Gas Heat
OFF
(Staged Gas
Heat)
Turn switch on to obtain only
high-gas-heat operation on
any call for heat regardless of
whether R-W/W1, or R-W/W1,
-W2 is closed. SW-1 overrides
SW-2.
SW-2
Low-Gas Heat
(Adaptive Mode)
OFF
(Single-Stage
Thermostat)
Turn switch off for installations
with single-stage thermostats;
control selects low-gas-heat
or high-gas-heat operation
based on previous cycles.
Turn switch on for installations
with 2-stage thermostats to
permit only low-gas-heat op-
eration in response to closing
R-W/W1. High-gas heat is
supplied only when R to
W/W1 and W2 is closed.
SW-3 and
SW4
ON, OFF
Switches control gas heating
blower off delay. (See Table
8.)
11