This furnace can be installed with either single-stage heating or
2-stage heating thermostat.
For single-stage thermostats, connect thermostat W to W/W1 at
furnace control terminal block. (See Fig. 15.) For single-stage
thermostats the control determines, based on length of previous
heating on and off cycles, when to operate in low- and high-gas
heat for optimum comfort. Setup Switch-2 (SW-2) must be in the
factory-shipped OFF position. See Fig. 17 and Tables 6 and 7 for
setup switch information.
If 2-stage heating thermostat is to be used, move SW-2 to ON
position at end of furnace installation. This overrides built-in
control process for selecting high and low stage and allows 2-stage
thermostat to select gas heating modes. The W2 from thermostat
must be connected to W2 on control terminal block. (See Fig. 16.)
Before operating furnace, check each manual reset switch for
continuity. If necessary, press and release button to reset switch.

Table 6—Electrical Data

UNIT

SIZE

VOLTS—

HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

MIN

WIRE

GAGE

MAX WIRE

LENGTH

FT‡

MAX FUSE OR

HACR-TYPE

CKT BKR AMPS†

Max*

Min*

065-08

115—60—1

127

104

8.0

14

46

15

065-12

115—60—1

127

104

10.5

14

35

15

085-12

115—60—1

127

104

12.0

14

30

15

085-16

115—60—1

127

104

14.2

14

26

15

105-16

115-60-1

127

104

13.2

14

29

15

105-20

115—60—1

127

104

17.2

12

33

20

125-20

115—60—1

127

104

17.9

12

32

20

* Permissible limits of the voltage range at which the unit will operate satisfactorily.

† Time-delay fuse is recommended.

‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.

Fig. 15—Heating and Cooling Application Wiring Diagram With 1-Stage Thermostat and Condensing Unit

A97443

115-V FUSED

DISCONNECT

SWITCH

(WHEN REQUIRED)

JUNCTION

BOX

CONTROL

BOX

24-V

TERMINAL

BLOCK

TWO-WIRE

HEATING-

ONLY

FIVE

WIRE

1-STAGE THERMOSTAT TERMINALS

FIELD-SUPPLIED

FUSED DISCONNECT

CONDENSING

UNIT

FURNACE

COM

R

W

Y

R

G

C

GND

GND

FIELD 24-V WIRING

FIELD 115-, 208/230-, 460-V WIRING

FACTORY 24-V WIRING

FACTORY 115-V WIRING

208/230- OR

460-V

THREE

PHASE

208/230-V

SINGLE

PHASE

WHT

BLK

WHT

BLK

W/W1

W2

Y/Y2

G

NOTES:

1. Connect Y-terminal as shown for proper operation.

2. Some thermostats require a "C" terminal connection as shown.

3. If any of the original wire, as supplied, must be replaced,

use same type or equivalent wire.

Table 7—Setup Switch Description

SETUP

SWITCH NO.

NORMAL

POSITION

DESCRIPTION OF USE

SW-1

Only High-Gas Heat

OFF

(Staged Gas

Heat)

Turn switch on to obtain only

high-gas-heat operation on

any call for heat regardless of

whether R-W/W1, or R-W/W1,

-W2 is closed. SW-1 overrides

SW-2.

SW-2

Low-Gas Heat

(Adaptive Mode)

OFF

(Single-Stage

Thermostat)

Turn switch off for installations

with single-stage thermostats;

control selects low-gas-heat

or high-gas-heat operation

based on previous cycles.

Turn switch on for installations

with 2-stage thermostats to

permit only low-gas-heat op-

eration in response to closing

R-W/W1. High-gas heat is

supplied only when R to

W/W1 and W2 is closed.

SW-3 and

SW4

ON, OFF

Switches control gas heating

blower off delay. (See Table

8.)

11