beautypg.com

SARGENT 2900 Fire Guard Electromechanical Closer-Holder User Manual

Page 5

background image

A7408B

5

Typical 12- Wiring with Alarm Panel Monitoring

(Class A) 4-Wire System by Others

• The alarm circuit monitors if smoke is detected

• The detector trouble circuit monitors if power is lost to the detector

NOTES: 1. End of line (EOL) resistor determined and supplied by others

2. Terminal numbers shown correspond to position numbers on terminal strip

3. Additional units may be added as required based on the schematic. See electrical data sheet. Do not overload circuits

4. Wires are added to header housing by inserting crimped terminal end into housing body until crimped terminal snaps

into position. Use accessory wire pack 63-3212

15

Earth ground to
track green wire

(+)

24VDC @ 0.15A Max.
to external alarm

(-)

(-)

(+)

Power
Supply
Board

1

2

(-)
(+)

Alarm

Circuit

Trouble

Circuit

EOL
RES

Alarm Panel

24VDC

Solenoid

24VDC @ 0.15A Max.
to external alarm

(+)
(-)

4

3

2

1

5

6

7

11

10

9

8

12

13

14

1

2

(-)
(+)

Power
Supply
Board

15

4

3

2

1

5

6

7

11

10

9

8

12

13

14

*

Connect to

power source

24VAC/DC

or 120VAC.

Power supply board

and power source

must match

(-)

(+)

24VDC

Solenoid

*

Earth ground to
track green wire

(-)

(+)

24VDC

Solenoid

Earth ground to
track green wire

Power
Supply
Board

1

2

(-)
(+)

*

24VDC @ 0.15A Max.
to external alarm

(+)
(-)

15

4

3

2

1

5

6

7

11

10

9

8

12

13

14