SARGENT 2900 Fire Guard Electromechanical Closer-Holder User Manual
Wiring instructions for the 2900 series fireguard, Wiring optional remote push button
Wiring Instructions for the
2900 Series FIREGUARD
®
Combination Door Closer-Holder and Releasing Device
with Integral Smoke Detector
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
CAUTION
INSTALLER: LEAVE INSTRUCTION with building owner.
•
Wire 12- smoke detector unit to appropriate
power supply and fire alarm
•
Refer to data sticker for proper input voltage
and current specifications
•
9- Companion units are designed to work with
12- smoke detector units (12-2960, 12-2990,
12-2980) only
•
Wire companion unit to 12- smoke detector
unit as shown on wiring diagram if required
•
Do not disconnect any existing wires on
smoke detector unit’s terminal strip
•
Energize power supply. Current draw
.1 AMP per 12- unit.
•
Open door(s) to hold-open point.
Door(s) should hold open
•
Depress On/Off test switch on circuit
board. Doors should close and latch
•
Adjustment of spring power may be
necessary to ensure proper latching
•
Depress On/Off test switch to
reactivate hold open latch
assembly(s)
A7408B
1
1. DISCONNECT ALL POWER BEFORE BEGINNING
INSTALLATION TO PREVENT ELECTRICAL SHOCK AND
EQUIPMENT DAMAGE.
2. INSTALLER MUST BE A TRAINED, EXPERIENCED
SERVICE PERSON.
3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL
ELECTRICAL CODES, ORDINANCES AND REGULATIONS.
4. MAXIMUM WIRE SIZE IS 18AWG.
Wiring 12- Units with and without 9- Companion Unit
9- Companion Unit
(If required)
Field wiring by others
Wire nut
On/Off Test switch
Yellow
Red
Black
Yellow
Black
Black
Terminal strip for
power input wiring
Red
Yellow
Smoke
detector
unit
12- Smoke Detector Unit
9
1112
14
3 7
RED LED/
Reset Switch
Data
Sticker
Opening
for
surface
or
concealed
wiring
Line
Neutral
Earth Ground
120VAC
Power
Supply
*120VAC
Circuit Board
shown
Self
resetting
fuse
Wire the appropriate Power Supply
to circuit board. Power is either
120VAC or 24VDC/VAC depending
on circuit board supplied.
When 24VDC/VAC board is supplied,
wire 24VDC/VAC power supply to
+ and - terminals on circuit board.
*CAUTION: Refer to data
sticker on circuit board for
proper input voltage required.
Do NOT wire 120VAC power
to 24VDC/VAC circuit board.
Earth ground connection is required
when 120VDC power is used
*120VAC
wiring shown
Circuit board 120VAC
or 24VAC/DC
(120VAC shown)
Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option
User supplied normally
closed momentary switch
Wiring Optional Remote Push Button