beautypg.com

SARGENT 2900 Fire Guard Electromechanical Closer-Holder User Manual

Wiring instructions for the 2900 series fireguard, Wiring optional remote push button

background image

Wiring Instructions for the

2900 Series FIREGUARD

®

Combination Door Closer-Holder and Releasing Device

with Integral Smoke Detector

CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.

For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com

CAUTION

INSTALLER: LEAVE INSTRUCTION with building owner.

Wire 12- smoke detector unit to appropriate
power supply and fire alarm

Refer to data sticker for proper input voltage
and current specifications

9- Companion units are designed to work with
12- smoke detector units (12-2960, 12-2990,
12-2980) only

Wire companion unit to 12- smoke detector
unit as shown on wiring diagram if required

Do not disconnect any existing wires on
smoke detector unit’s terminal strip

Energize power supply. Current draw
.1 AMP per 12- unit.

Open door(s) to hold-open point.
Door(s) should hold open

Depress On/Off test switch on circuit
board. Doors should close and latch

Adjustment of spring power may be
necessary to ensure proper latching

Depress On/Off test switch to
reactivate hold open latch
assembly(s)

A7408B

1

1. DISCONNECT ALL POWER BEFORE BEGINNING

INSTALLATION TO PREVENT ELECTRICAL SHOCK AND
EQUIPMENT DAMAGE.

2. INSTALLER MUST BE A TRAINED, EXPERIENCED

SERVICE PERSON.

3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL

ELECTRICAL CODES, ORDINANCES AND REGULATIONS.

4. MAXIMUM WIRE SIZE IS 18AWG.

Wiring 12- Units with and without 9- Companion Unit

9- Companion Unit
(If required)

Field wiring by others

Wire nut

On/Off Test switch

Yellow

Red

Black

Yellow

Black

Black

Terminal strip for
power input wiring

Red

Yellow

Smoke
detector
unit

12- Smoke Detector Unit

9

1112

14

3 7

RED LED/
Reset Switch

Data
Sticker

Opening
for
surface
or
concealed
wiring

Line

Neutral

Earth Ground

120VAC

Power

Supply

*120VAC
Circuit Board
shown

Self
resetting
fuse

Wire the appropriate Power Supply
to circuit board. Power is either
120VAC or 24VDC/VAC depending
on circuit board supplied.

When 24VDC/VAC board is supplied,
wire 24VDC/VAC power supply to
+ and - terminals on circuit board.

*CAUTION: Refer to data
sticker on circuit board for
proper input voltage required.

Do NOT wire 120VAC power
to 24VDC/VAC circuit board.

Earth ground connection is required
when 120VDC power is used

*120VAC

wiring shown

Circuit board 120VAC
or 24VAC/DC
(120VAC shown)

Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option

User supplied normally
closed momentary switch

Wiring Optional Remote Push Button