Misc menu – tekmar 541 Thermostat User Manual
Page 10

© 2007
D 541 - 08/07
10 of 24
Item Field
Range
Access
Description
-5.0 to +5.0°F in
0.1°F increments
(-3.0° to +3.0°C in
0.1°C increments)
Default = 0.0°F
ADV
OFFSET
SECTION
L
Fine tune the current room temperature. Adjustments
are in tenths of a degree.
– – –, -bus#:01,
... bus#:24, DEF
Default = – – –
INST
ADV
COPY SETTINGS
Copy settings from another thermostat to this
thermostat.
1. Select the address of the thermostat to copy from.
Select DEF to load the factory default settings.
2. Wait for 3 seconds and then press the Up and Down
buttons for 1 second.
3. The thermostat will show the percentage of progress.
4. Displays DONE if successful or WARN if only part
of the settings were copied.
1 to 24
ADV
NUMBER OF DEVICES
Number of tN4 devices connected to this tN4 bus.
Note: This item is only available when the thermostat
is connected to a tN4 bus.
AUTO, -bus#:01,
... bus#:24
Default = AUTO
SEC
LTD
USER
INST
ADV
ADDRESS
SECTION
O
The tN4 bus address of this thermostat.
Auto allows the tN4 system to automatically assign
an address to the thermostat.
To manually set the address, use the Up or Down
buttons while in the ADV or INST access level.
Note: This item is only available when the thermostat
is connected to a tN4 bus.
541, Software Version
SEC
LTD
USER
INST
ADV
TYPE
Product number of this thermostat. Hold the Up button
to view the software version.
Misc (Miscellaneous) Menu (2 of 2)
After the last item, the control returns to the first item in the menu.
MISC MENU