Device configuration – Banner SureCross DX85 Expandable Remote I/O User Manual
Page 5
I/O
Modbus Holding Register
I/O Type
Units
I/O Range
Holding Register
Representation
Terminal
Block La-
bels
Gateway /
DX85
Any Node
Min.
Value
Max.
Value
Min.
(Dec.)
Max.
(Dec.)
5
5
5 + (Node# × 16)
Discrete IN 5
-
0
1
0
1
DI5
6
6
6 + (Node# × 16)
Discrete IN 6
-
0
1
0
1
DI6
7
7
7 + (Node# × 16)
Reserved
8
8
8 + (Node# × 16)
Device Message
9
9
9 + (Node# × 16)
Discrete OUT 1
-
0
1
0
1
DO1
10
10
10 + (Node# × 16)
Discrete OUT 2
-
0
1
0
1
DO2
11
11
11 + (Node# × 16)
Discrete OUT 3
-
0
1
0
1
DO3
12
12
12 + (Node# × 16)
Discrete OUT 4
-
0
1
0
1
DO4
13
13
13 + (Node# × 16)
Discrete OUT 5
-
0
1
0
1
DO5
14
14
14 + (Node# × 16)
Discrete OUT 6
-
0
1
0
1
DO6
15
15
15 + (Node# × 16)
Control Message
16
16
16 + (Node# × 16)
Reserved
Device Configuration
Setting the Slave ID on a DX85 Remote I/O Device
On a DX85 Modbus RTU Remote I/O device, use the rotary dials to set the device’s Slave ID.
In Rotary Dial Decimal Mode, the left dial acts as the left digit and the right dial acts as the right
digit, allowing the Slave ID to be set from 01 through 99.
In Rotary Dial Hex Mode, the left dial acts as the left digit and the right dial acts as the right digit,
allowing the Slave ID to be set from 01 through F7 for a total of 247 slaves.
The 12 I/O DX85 models use Rotary Dial Decimal Mode and do not have a DIP switch selection
for this option.
To configure the DX85 using the UCT, the DX85's Slave ID must be set to 01.
DIP Switch Changes
Before making any changes to the DIP switch positions, disconnect
the power. For devices with batteries integrated into the housing,
remove the battery for at least one minute.
DIP switch changes will not be recognized if power isn't cycled to
the device.
Accessing the DIP Switches
To access the DIP switches, follow these steps:
1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
SureCross DX85 Modbus RTU Remote I/O Device
P/N 131599 rev. G
www.bannerengineering.com - tel: 763-544-3164