Device configuration – Banner SureCross DX85 Expandable Remote I/O User Manual

Page 5

background image

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register
Representation

Terminal

Block La-

bels

Gateway /

DX85

Any Node

Min.
Value

Max.
Value

Min.
(Dec.)

Max.
(Dec.)

5

5

5 + (Node# × 16)

Discrete IN 5

-

0

1

0

1

DI5

6

6

6 + (Node# × 16)

Discrete IN 6

-

0

1

0

1

DI6

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Discrete OUT 1

-

0

1

0

1

DO1

10

10

10 + (Node# × 16)

Discrete OUT 2

-

0

1

0

1

DO2

11

11

11 + (Node# × 16)

Discrete OUT 3

-

0

1

0

1

DO3

12

12

12 + (Node# × 16)

Discrete OUT 4

-

0

1

0

1

DO4

13

13

13 + (Node# × 16)

Discrete OUT 5

-

0

1

0

1

DO5

14

14

14 + (Node# × 16)

Discrete OUT 6

-

0

1

0

1

DO6

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Device Configuration

Setting the Slave ID on a DX85 Remote I/O Device

On a DX85 Modbus RTU Remote I/O device, use the rotary dials to set the device’s Slave ID.

In Rotary Dial Decimal Mode, the left dial acts as the left digit and the right dial acts as the right
digit, allowing the Slave ID to be set from 01 through 99.
In Rotary Dial Hex Mode, the left dial acts as the left digit and the right dial acts as the right digit,
allowing the Slave ID to be set from 01 through F7 for a total of 247 slaves.
The 12 I/O DX85 models use Rotary Dial Decimal Mode and do not have a DIP switch selection
for this option.
To configure the DX85 using the UCT, the DX85's Slave ID must be set to 01.

DIP Switch Changes

Before making any changes to the DIP switch positions, disconnect
the power. For devices with batteries integrated into the housing,
remove the battery for at least one minute.
DIP switch changes will not be recognized if power isn't cycled to
the device.

Accessing the DIP Switches

To access the DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.

SureCross DX85 Modbus RTU Remote I/O Device

P/N 131599 rev. G