Modbus register table, Terminal block (ip20 base), Wiring diagrams for discrete inputs – Banner SureCross DX85 Expandable Remote I/O User Manual

Page 4: Wiring diagrams for discrete outputs

background image

Terminal Block (IP20 Base)

DI1
DI2
DI3
DI4
DI5
DI6
V+

V−
V−

DO1
DO2
DO3
DO4
DO5
DO6
TX/+

RX/−
V+

DIx. Discrete IN x.
DOx. Discrete OUT x.
RX/-. Serial comms line
TX/+. Serial comms line
V+. Power, 10 to 30V dc power connection.
V-. Ground/dc common connection.

Wiring Diagrams for Discrete Inputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.

Discrete Input Wiring (PNP)

Discrete Input Wiring (NPN)

DIx

PWR or SPx

SureCross Device

DIx

GND

SureCross Device

Wiring Diagrams for Discrete Outputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.

Discrete Output Wiring (PNP)

DOx

GND

SureCross Device

Modbus Register Table

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register
Representation

Terminal

Block La-

bels

Gateway /

DX85

Any Node

Min.
Value

Max.
Value

Min.
(Dec.)

Max.
(Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

-

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

-

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Discrete IN 3

-

0

1

0

1

DI3

4

4

4 + (Node# × 16)

Discrete IN 4

-

0

1

0

1

DI4

SureCross DX85 Modbus RTU Remote I/O Device

4

www.bannerengineering.com - tel: 763-544-3164

P/N 131599 rev. G