Data summary, Table 20 example 3 - output data summary, Table 21 example 3 - input data summary – Rockwell Automation T8017 Trusted Peer to Peer Communications User Manual
Page 42: Trusted, Communication software package t8017
Trusted
TM
Communication Software Package T8017
Issue 10 Mar 08
PD-T8017
42
2.5.2.
Data Summary
Output data summary
Controller 1
Controller 2
Controller 3
Controller 4
DATA rack
dxpao
dxpao
dxpdo
dxpdo
dxpdo
NETWORK_ID
1
1
1
1
2
TARGET_PEER_ID
2
3
4
5
2
SOURCE_DATA_ID
1
2
1
1
1
REFRESH_TMO
2000
2000
2000
2000
2000
MIN_DELTA
20
20
Variable 1 - 16
Analogue
Data Output
Analogue
Data Output
Digital Data
Output
Digital Data
Output
Digital Data
Output
Table 20 Example 3 - Output data summary
Input data summary
Controller
1
Controller 2
Controller
3
Controller 4
Controller 5
DATA rack
dxpdi
dxpdi
dxpai
dxpai
dxpdi
dxpdi
dxpdi
NETWORK_ID
1
1
1
1
1
1
2
SOURCE_PEER_ID
3*
3*
1
1
3*
2
1
SOURCE_DATA_ID
1
1
1
2
1
1
1
REFRESH_TMO
5000
5000
5000
5000
5000
5000
5000
FS_VALUE
FALSE
FALSE
-1024
-1024
FALSE
FALSE
FALSE
Variable 1 - 16
Boolean
Data Input
Boolean
Data Input
Analogue
Data Input
Analogue
Data Input
Boolean
Data Input
Boolean
Data Input
Boolean
Data Input
STATUS rack
Variable 1
Input data
valid
Input data
valid
Input data
valid
Input data
valid
Input data
valid
Input data
valid
Input data
valid
Variable 2 - 9
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
CONTROL rack
Variable 1
Failure
action
Failure
action
Failure
action
Failure
action
Failure
action
Failure
action
Failure
action
Table 21 Example 3 - Input data summary
* Multi cast data receive from controller 3. The communication modules for network 1 on controllers 1,
2 and 4 must have the multicast IP address added to the communication module multicast address list;
refer to Multicast Configuration in PD-T8151B.