Trusted, Communication software package t8017 – Rockwell Automation T8017 Trusted Peer to Peer Communications User Manual
Page 33
![background image](/manuals/581640/33/background.png)
Trusted
TM
Communication Software Package T8017
Issue 10 Mar 08
PD-T8017
33
Dual Peer to Peer Analogue Output (data is sent via both subnets automatically).
dxpao – DATA rack
Value
Comment
NETWORK_ID
1
Network 1
TARGET_PEER_ID
2
This output is going to PEER_IP_02.
SOURCE_DATA_ID
1
Will transmit data ID 1. This is a unique packet ID to
enable the system to distinguish between different data
packets routed between the same source and
destination.
REFRESH_TMO
2000
Maximum time peer data is sent if no change of
application values above the MIN_DELTA has
occurred.
MIN_DELTA
20
The value change that is required before the data will
be transmitted. If the value change is less than this, the
value will be transmitted based on the
REFRESH_TMO setting.
Variable 1 - 16
Analogue
Output
Analogue output points.
Table 10 Example 2 - PEER_IP_02 Analogue Output (data sent automatically)
Dual Peer to Peer Analogue Output (data is sent via both subnets automatically).
dxpao – DATA rack
Value
Comment
NETWORK_ID
1
Network 1
TARGET_PEER_ID
3
This output is going to PEER_IP_03.
DATA_ID
2
Will transmit data ID 1. This is a unique packet ID to
enable the system to distinguish between different data
packets routed between the same source and
destination.
REFRESH_TMO
2000
Maximum time peer data is sent if no change of
application values above the MIN_DELTA has
occurred.
MIN_DELTA
20
The value change that is required before the data will
be transmitted. If the value change is less than this, the
value will be transmitted based on the REFRESH_TMO
setting.
Variable 1 - 16
Analogue
Output
Analogue output points.
Table 11 Example 2 - PEER_IP_03 Analogue Output (data sent automatically)