2.4.3.
Data Summary
Output data summary
Controller 1
Controller 2
Controller 3
DATA rack
dxpao
dxpao
dxpdo
dxpdo
NETWORK_ID
1
1
1
1
TARGET_PEER_ID
2
3
4
5
SOURCE_DATA_ID
1
2
1
1
REFRESH_TMO
2000
2000
2000
2000
MIN_DELTA
20
20
Variable 1 - 16
Analogue
Data
Output
Analogue
Data Output
Digital Data
Output
Digital Data
Output
Table 14 Example 2 - Output Data Summary
Input data summary
Controller
1
Controller 2
Controller 3
Controller 4
DATA rack
dxpdi
dxpdi
dxpai
dxpai
dxpdi
dxpdi
NETWORK_ID
1
1
1
1
1
1
SOURCE_PEER
3*
3*
1
1
3*
2
SOURCE_DATA_ID
1
1
1
2
1
1
REFRESH_TMO
5000
5000
5000
5000
5000
5000
FS_VALUE
FALSE
FALSE
-1024
-1024
FALSE
FALSE
Variable 1 - 16
Boolean Data
Input
Boolean
Data Input
Analogue
Data Input
Analogue Data
Input
Boolean
Data Input
Boolean
Data Input
STATUS rack
Variable 1
Input data
valid
Input data
valid
Input data
valid
Input data valid
Input data
valid
Input data
valid
Variable 2 - 9
Refreshed on
subnet 1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed on
subnet 1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
CONTROL rack
Variable 1
Failure action
Failure
action
Failure
action
Failure action
Failure
action
Failure
action
Table 15 Example 2 - Input data summary
* Multi cast data receive from controller 3. The communication modules for network 1 on controllers 1,
2 and 4 must have the multicast IP address added to the communication module multicast address list;
refer to Multicast Configuration in PD-T8151B.