Peer to peer configuration example 2, Controller 1 settings, Trusted – Rockwell Automation T8017 Trusted Peer to Peer Communications User Manual
Page 30: Communication software package t8017

Trusted
TM
Communication Software Package T8017
Issue 10 Mar 08
PD-T8017
30
2.4. Peer to Peer Configuration Example 2
Figure 13 shows an example configuration for a system using 4 controllers connected together
using one peer to peer network with dual physical network paths, but this time with multicast
data.
In this example, Controller 4 will be the master of network 1 subnet 1. Controller 1 will be the
master of network 1 subnet 2.
• 16 digital points will be sent from controller 3 to controllers 1, 2 & 4 via a multicast
configuration.
• 16 analogue points will be sent from controller 1 to controller 2.
• A separate set of 16 analogue values will be sent from controller 1 to controller 3.
• 16 digital values will be sent from controller 2 to controller 4.
2.4.1.
Controller 1 settings
Dual Peer to Peer Net Control, network 1 subnet 1.
dxpnc40 –
CONTROL rack
Value
Comment
CHASSIS
1
Communication module located in chassis 1.
SLOT
7
Communication module is located in slot 7.
NETWORK_ID
1
Network 1
SUBNET_ID
1
Subnet 1
PEER_ID
1
Identity of this controller.
RESPONSE_TMO
0
Default
REFRESH_TMO
2000
Default
TX_DATA_TMO
500
Default
Variable 1
TRUE
Enable Peer to on this subnet.
Variable 2
FALSE
This is a slave connection.
PEERS_1 rack
PEER_IP_01
10.10.1.1
Controller 1, network 1, subnet 1
PEER_IP_02
10.10.1.2
Controller 2, network 1, subnet 1
PEER_IP_03
10.10.1.3
Controller 3, network 1, subnet 1
PEER_IP_04
10.10.1.4
Controller 4, network 1, subnet 1
PEER_IP_05
239.255.1.1
Multicast address
Table 7 Example 2 - Controller 1 Settings Control, network 1 subnet 1