Rockwell Automation AADvance Controller System Build User Manual
Page 88

4-8
Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
System Build Manual (AADvance Controller)
Ready
GREEN
Run
AMBER
Channel 1 – 8
Off
6.
Press the Fault Reset button on the processor module and the Run indication goes GREEN.
7.
The module will now be on-line with the following status indications:
Healthy
GREEN
Ready
GREEN
Run
GREEN
Channel 1 – 8)
Dependent on channel status
8.
If the module fails to educate and go on-line replace the module.
Table 11:
Table 11:
Table 11:
Table 11:
Second or third Module of a Group Installation Procedure
Second or third Module of a Group Installation Procedure
Second or third Module of a Group Installation Procedure
Second or third Module of a Group Installation Procedure
Step
Task
1.
This procedure applies to a second or third module of a redundant group.
2
Install the Input/Output Module and turn the locking screw to the lock position.
3.
The input module will provide the following status indications:
Healthy
GREEN
Ready
RED
Run
RED
Channel 1 – 8
Off
4.
The input module will enter its start up sequence during which the module will educate.
Wait for approximately 3 seconds.
5.
The module will now provide the following status indications:
Healthy
GREEN
Ready
GREEN
Run
AMBER
Channel 1 – 8
Off
6.
Press the Fault Reset button on the processor module and the Run indication goes GREEN.
7.
The module will now be on-line with the following status indications:
Healthy
GREEN
Ready
GREEN
Run
GREEN
Channel 1 – 8)
Dependent on channel status