Rockwell Automation AADvance Controller System Build User Manual
Page 87

Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
4-7
Step Task
When the Run indicator goes AMBER press the Fault Reset button and the processor will display the
following indications:
2.
Healthy
Green
Ready
GREEN (can flash for a short time as the module educates)
Run
AMBER to GREEN (AMBER as the module educates)
System Healthy
GREEN
Force
Off to GREEN
Aux
Off (application dependent)
Serial 1
Dependent on Data Connection
Serial 2
Dependent on Data Connection
Ethernet 1
Dependent on Data Connection
Ethernet 2
Dependent on Data Connection
3.
To insert a 3rd processor module repeat step 1 and insert in Slot C.
I/O Module Start Up Process
I/O Module Start Up Process
I/O Module Start Up Process
I/O Module Start Up Process
To start up an Input/Output Module follow this procedure:
Note: The start up sequence is different when a module is installed into an on-line
system that is running compared to installing the module into a system that is off-line
and has processor modules but no I/O modules installed. The first part of this
procedure covers the initial start up of an off-line system, the second part covers a
system that is on line and you are adding I/O modules.
Table 10:
Table 10:
Table 10:
Table 10:
Single
Single
Single
Single Module or First Module of a group Installation Procedure
Module or First Module of a group Installation Procedure
Module or First Module of a group Installation Procedure
Module or First Module of a group Installation Procedure
Step
Task
1.
This procedure applies to a single module installed or the first module of a redundant group.
2
Install the Input/Output Module and turn the locking screw to the lock position.
3.
The input module will provide the following status indications:
Healthy
GREEN
Ready
RED
Run
RED
Channel 1 – 8
Off
4.
The input module will enter its start up sequence during which the module will educate.
Wait for approximately 3 seconds.
5.
The module will now provide the following status indications:
Healthy
GREEN