Module – mai32lad (0-5v; analogue input module), Trusted™ bridge module 8161 – Rockwell Automation SC300E Trusted Bridge Module User Manual
Page 19
Trusted™ Bridge Module 8161
Issue 2 Feb 10
PD-8161
19
3.2.3 Module – mai32lad (0-5V; analogue input Module)
DESCRIPTION
This definition will open a single MAI32LAD.
OEM PARAMETERS
OEM parameter
Valid numbers
Description
CHASSIS
2-29
Logical chassis and slot number where the
SLOT
1-10
MAI32LAD is located.
PHYSICAL MODULE:
RACK 1: (AI)
32 INTEGER inputs
RACK 2: (DIAG)
3 INTEGER inputs
Word 1 Health status bits, 0=healthy 1=fault
bit 0-2
Microcontroller watchdog (bit 0=A, bit 1=B, bit2=C)
bit 3-5
MP watchdog (bit 0=A, bit 1=B, bit2=C)
bit 6-8
Microcontroller slice health (bit 0=A, bit 1=B, bit2=C)
bit 9-11
Combined slice health (bit 0=A, bit 1=B, bit2=C)
bit 12
Power Fail
bit 13-15
not used
Word 2 Diagnostic bits
bit 0
Slice A
=1
slice is not responding or there is an error
=0
slice is responding
bit 1
Slice B
=1
slice is not responding or there is an error
=0
slice is responding
bit 2
Slice C
=1
slice is not responding or there is an error
=0
slice is responding
bit 3
Module offline or missing
=1
offline or missing
=0
online
bit 4
Single slot hot repair
=1
in progress
=0
not in progress
bit 5
Discrepancy errors
=1
faults detected
=0
no faults detected
bit 6
LFD faults
=1
faults detected
=0
no faults detected
Word 3 Slot number of active module
RACK 3: (FAULTS)
4 INTEGER inputs
Word 1
Discrepancy errors, channels 1-16 (bit 0 = channel 1)
Word 2
Discrepancy errors, channels 17-32 (bit 0 = channel 17)
Word 3
LFD errors, channels 1-16 (bit 0 = channel 1)
Word 4
LFD errors, channels 17-32 (bit 0 = channel 17)