Application, System configuration, Figure 8 insert new chassis – Rockwell Automation SC300E Trusted Bridge Module User Manual
Page 12: 1 system configuration
Trusted™ Bridge Module 8161
Issue 2 Feb 10
PD-8161
12
3. Application
All Triguard I/O modules are configured using the IEC1131 application Toolset provided with
Trusted™. This configuration requires entries in the System Configuration (System.INI) for the chassis
and modules and their hardware operational parameters, and also in the workbench I/O connection
table, for software settings and data connection.
3.1 System Configuration
All Trusted™ systems need a system configuration file, specifying the chassis and modules in the
system. For Trusted™/Triguard hybrid systems, a T8311 Expander Interface is required in the
Trusted™ controller chassis, as for Trusted™-only systems. An example with Expander Interfaces in
slots 1 and 2 (companion slots) and communications interfaces in slots 7 and 8, is shown below. For
details of the System Configuration Tool please refer to product description PD-T8082.
Figure 7 Trusted™ Processor Chassis with Expander Interface
The Triguard chassis are attached to the Expander Interface as if they were Trusted™ expander
chassis, but the various chassis options for Triguard and CS300 are provided on the ‘Insert New
Chassis’ dialog. Right-click on the grey background of the configurator window to insert a new chassis.
Figure 8 Insert New Chassis