beautypg.com

Module – 8161 (bridge module), Trusted™ bridge module 8161 – Rockwell Automation SC300E Trusted Bridge Module User Manual

Page 17

background image

Trusted™ Bridge Module 8161

Issue 2 Feb 10

PD-8161

17

3.2.1 Module – 8161 (Bridge Module)

DESCRIPTION
This definition provides module status for a Logical Triguard 8161 primary chassis expansion interface
module.
The logical module accounts for the 3 physical modules FCR-A, FCR-B and FCR-C.

OEM PARAMETERS:

OEM parameter

Valid numbers

Description


CHASSIS

2-29

Logical chassis number allocated to the primary
Triguard chassis in which the 8161 modules
are placed.


SLOT

15

Logical slot within the Primary Triguard chassis
by which the 8000 system identifies the 8161
module. This cannot be configured.


PHYSICAL MODULE:

RACK 1: [STATUS] - 6 BOOL Inputs

Variable 1:

TRUE = Logical module responding

Variable 2:

TRUE = FCR-A faulted or not responding

Variable 3:

TRUE = FCR-B faulted or not responding

Variable 4:

TRUE = FCR-C faulted or not responding

Variable 5:

TRUE = Power supply 1 faulted

Variable 6:

TRUE = Power supply 2 faulted


RACK 2: [INFO] - 12 ANALOGUE Inputs

Word 1:

FCR-A fault code (see note 1)

Word 2:

FCR-B fault code (see note 1)

Word 3:

FCR-C fault code (see note 1)

Word 4:

FCR-A hot-link error count

Word 5:

FCR-B hot-link error count

Word 6:

FCR-C hot-link error count

Word 7:

FCR-A IML own-link error count

Word 8:

FCR-A IML down-link error count

Word 9:

FCR-A IML up-link error count

Word 10:

FCR-B IML own-link error count

Word 11:

FCR-B IML down-link error count

Word 12:

FCR-B IML up-link error count

Word 13:

FCR-C IML own-link error count

Word 14:

FCR-C IML down-link error count

Word 15:

FCR-C IML up-link error count

[Note 1 - Fault Codes]

0

: No fault

1

: Local backplane fault

2

: Local expansion bus fault

3

: Common fault (applies to both local backplane and expansion busses)