Module – 8161 (bridge module), Trusted™ bridge module 8161 – Rockwell Automation SC300E Trusted Bridge Module User Manual
Page 17
Trusted™ Bridge Module 8161
Issue 2 Feb 10
PD-8161
17
3.2.1 Module – 8161 (Bridge Module)
DESCRIPTION
This definition provides module status for a Logical Triguard 8161 primary chassis expansion interface
module.
The logical module accounts for the 3 physical modules FCR-A, FCR-B and FCR-C.
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
CHASSIS
2-29
Logical chassis number allocated to the primary
Triguard chassis in which the 8161 modules
are placed.
SLOT
15
Logical slot within the Primary Triguard chassis
by which the 8000 system identifies the 8161
module. This cannot be configured.
PHYSICAL MODULE:
RACK 1: [STATUS] - 6 BOOL Inputs
Variable 1:
TRUE = Logical module responding
Variable 2:
TRUE = FCR-A faulted or not responding
Variable 3:
TRUE = FCR-B faulted or not responding
Variable 4:
TRUE = FCR-C faulted or not responding
Variable 5:
TRUE = Power supply 1 faulted
Variable 6:
TRUE = Power supply 2 faulted
RACK 2: [INFO] - 12 ANALOGUE Inputs
Word 1:
FCR-A fault code (see note 1)
Word 2:
FCR-B fault code (see note 1)
Word 3:
FCR-C fault code (see note 1)
Word 4:
FCR-A hot-link error count
Word 5:
FCR-B hot-link error count
Word 6:
FCR-C hot-link error count
Word 7:
FCR-A IML own-link error count
Word 8:
FCR-A IML down-link error count
Word 9:
FCR-A IML up-link error count
Word 10:
FCR-B IML own-link error count
Word 11:
FCR-B IML down-link error count
Word 12:
FCR-B IML up-link error count
Word 13:
FCR-C IML own-link error count
Word 14:
FCR-C IML down-link error count
Word 15:
FCR-C IML up-link error count
[Note 1 - Fault Codes]
0
: No fault
1
: Local backplane fault
2
: Local expansion bus fault
3
: Common fault (applies to both local backplane and expansion busses)