Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual
Page 18
18 XM ControlNet Adapter
Publication
ICM-IN001A-EN-P - March 2009
(1)
See the Product Certification link at
for Declarations of Conformity, Certificates,
and other certification details.
Surge Transient Immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV
line-earth(CM) on power ports
±2 kV line-earth(CM) on communications
ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Certifications
(when product is marked)
Certifications
(1)
Description
c-UL-us
UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File
E194810.
CE
European Union 2004/108/EC EMC Directive, compliant
with:
• EN 61326-1; Meas./Control/Lab., Industrial
Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8,
Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres,
Protection "n" (II 3 G Ex nA IIC T4 X)
• EN 60079-0; General Requirements (Zone 2)
CI
ControlNet Int'l conformance tested to ControlNet
specifications
Environmental Specifications
Attribute
Value