beautypg.com

Specifications – Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual

Page 16

background image

16 XM ControlNet Adapter

Publication

ICM-IN001A-EN-P - March 2009

Specifications

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

XM ControlNet Adapter - 1440-ACNR

Attribute

Value

Enclosure Type Rating

None (open-style)

Input Voltage

24V DC
Current Draw Max 120 mA

XM Bus Output

24V DC, 3 A Max

Isolation Voltage

50V (continuous), Basic Insulation Type
Type tested at 900V AC for 60 s, between
ControlNet to system and ControlNet to
power.

Wire Size

Power connections:

0.34... 2.1 mm

2

(22...14 AWG) solid or

stranded copper wire rated at 75 °C (167
°F ) or greater 1.2 mm (3/64 in.) insulation
max

Wiring Category

(1)

1 - on power ports
2 - on communications ports

North American Temp Code

T4A

IEC Temp Code

T4

Environmental Specifications

Attribute

Value

Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):

-20…70 °C (-4…158 °F)