XM ControlNet Adapter 11

Publication

ICM-IN001A-EN-P - March 2009

2. Connect the redundant ControlNet network cable to connector B.

3. Connect +V DC power to the lower connector, terminal F or D.

4. Connect -V common to the upper connector, terminal E or C.

Set the Node Address

Set the network address using the 2-button pushwheel switch (G). Valid
settings range from 01 to 99.

ATTENTION

When connecting wiring, torque terminal screws C, D, E, and F to 0.8 Nm
(7 lb-in).

2

5

Press either the + or
- buttons to change
the number.

Network
Address
Switches