Setting the Current Rating Jumpers (J13 through
J16)
Jumpers J13 through J16 set the maximum continuous current rating and the
associated current limit level of the drive’s output current. The four jumpers are binary
weighted and scaled so that the current limit level is adjustable from 30 to 70 amps
RMS in approximate 3 amp RMS steps. Table 2.3.6 shows the nominal current limit
level for each possible jumper setting.
Table 2.3 – Current Rating Jumper Settings
Jumpers
Rated
Continuous
Current
Current Limit
Threshold
1
1
Eventual drive shutdown if sustained
Current Limit
(A RMS)
(1 minute
Instantaneous
Overcurrent Trip
J13
J14
J15
J16
(A RMS)
(A RMS)
allowable)
(A Peak)
0
0
0
0
30
>30
39
68
0
0
0
1
33
>33
42
75
0
0
1
0
35
>35
46
80
0
0
1
1
38
>38
49
86
0
1
0
0
41
>41
53
93
0
1
0
1
43
>43
56
98
0
1
1
0
46
>46
59
105
0
1
1
1
49
>49
63
112
1
0
0
0
51
>51
66
116
1
0
0
1
54
>54
70
123
1
0
1
0
57
>57
73
130
1
0
1
1
59
>59
76
134
1
1
0
0
62
>62
80
141
1
1
0
1
63
2
2
The user must verify that the application does not exceed the maximum continous rating of 63 A RMS. Exceeding this rating could cause
overtemperature protection to shut down the drive. For maximum system protection, it is recommended that the current limit jumpers be
set to a value not greater than the application demands.