Install the computer, Panel mounting guidelines, Panel cutout dimensions – Rockwell Automation 6181F_P Series E Integrated Display Computers Installation Instructions User Manual
Page 13

Industrial Integrated Display Computers 13
Rockwell Automation Publication 6181P-IN010F-EN-P - July 2013
Install the Computer
The computers support the following mounting options:
• Panel mount
• Wall mount (for non-display computers)
Panel Mounting Guidelines
Observe these guidelines when installing the computer in a panel:
• Remove all electrical power from the panel before making the cutout.
• Confirm that there is adequate space behind the panel. For specific information, refer to
• Cut supporting panels to specifications before installation. Take precautions so metal
cuttings do not enter components already installed in panel.
Supporting panels must be at least 14 gauge for proper sealing against water and dust,
and to provide proper support. The mounting hardware supplied accommodates panel
thickness 1.5…5.5 mm (0.06…0.25 in.).
• Make sure the area around the panel cutout is clear.
Panel Cutout Dimensions
The computers must be mounted to meet the panel cutout dimensions specified below.
Included with the computer is 6181P and 6181X Industrial Computers Cutout Template,
publicat
, with a cutout template for each display computer model.
ATTENTION: Failure to follow these guidelines can result in personal injury or damage to the panel
components.
Computer Model
Cutout Dimensions (H x W), approx
1200P
254.0 x 324.0 mm (10.0 x 12.76 in.)
1500P
285.0 x 386.6 mm (11.24 x 15.22 in.)
1700P
329.5 x 424.0 mm (12.97 x 16.69 in.)