Preventing electrostatic discharge, About the board – Rockwell Automation 1799-OQ10X Embedded I/O Expansion Board with 10 Outputs User Manual
Page 4

4 Embedded I/O Expansion Board with 10 Outputs
Publication
1799-IN013B-EN-P - May 2013
About the Board
The 1799-OQ10X is an expansion 10-point Output board that works only with
1799ER-IQ10XOQ10 as an expansion I/O module.
This board has 10 outputs, that are self-protected 24V DC sinking or sourcing.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
•
Touch a grounded object to discharge potential static.
•
Wear an approved grounding wriststrap.
•
Do not touch connectors or pins on component boards.
•
Do not touch circuit components inside the equipment.
•
Use a static-safe workstation, if available.
•
Store the equipment in appropriate static-safe packaging when not in
use.
ATTENTION
Do not wire more than 2 conductors on any single terminal.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this equipment and all
connected I/O must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION
To comply with UL restrictions, this equipment and all connected I/O must be
powered from a source compliant with the following:
10…30V DC Class 2 Power Supply or a 10…30V DC UL Listed or Recognized
Power Supply with isolated outputs limited to 200 volt-amperes in each
ungrounded output line. This equipment and its power source must be
mounted in a suitable enclosure with proper spacings maintained.