3 local i/o head with automate remote i/o head – Rockwell Automation 61C23 AutoMate Local I/O Head User Manual
Page 15

4Ć3
4.3
Local I/O Head with AutoMate Remote
I/O Head
When using the Local I/OHead with the AutoMate Remote I/OHead,
only the first register of the four that are needed for the configuration
needs to be specified. The Executive software automatically assigns
the next three contiguous registers for the configuration. Note that
even if only one port of the Head is being used, four contiguous
registers are still reserved for the configuration. See below for a
sample configuration.
Sample configuration with four Rails connected to the Local I/O
Head, the AutoMate Remote I/OHead in drop 6, and the Remote I/O
Processor (master) in slot 3 of the master rack.
MSLT
DROP
TYPE
RSLOT CARD CH0
REG
CH1
REG
CH2
REG
CH3
REG
3
6
RHD
LHD
0Ć3
LHD
4Ć7
LHD
10Ć13 LHD
14Ć17
4.4
Local I/O Head with DCS 5000/AutoMax
Remote I/O Head
When using the Local I/OHead with the DCS 5000/AutoMax Remote
I/OHead, the Local I/OHead is configured in the configuration for
the rack which contains the DCS 5000/AutoMax Remote I/Omaster
module (M/N 57C416). If you are using AutoMax Version 2.1 or
earlier, see below for the format of the statement used in the
configuration task. If you are using AutoMax Version 3.0 or later, the
Local I/OHead is configured using the AutoMax Programming
Executive.
Note that you cannot mix input and output modules in Rails
connected to the Local I/OHead when it is connected to a DCS
5000/AutoMax Remote I/OHead. You also cannot use the Analog
Rail modules (M/N 61C350, 61C351, etc.)in this configuration.
nnnnn RIODEF name[MASTER_SLOT=m, DROP=d, SLOT=s, &
REGISTER=r, Bit=b]
where:
nnnnn Ć
Configuration task line number. This number may range
from 1 to 32767.
name Ć
Symbolic name of register or bit, ending with % (integer)
for registers or @ (boolean) for bits.