4.0 CONFIGURATION

Configuration is a method of describing how the system software and

the I/O are related. The process of configuring the Local I/O Head is

dependent upon the host. If the host is an AutoMate, use the

AutoMate Programming Executive Software (M/N 45C130 or M/N

45C131) to perform the configuration. Note that the registers in which

the configuration will be stored are dependent upon the register

assignments of the particular model number.
If the Local I/O Head will be communicating through the DCS

5000/AutoMax Remote I/O Head with a DCS 5000 or AutoMax host,

use the appropriate Executive software to create the configuration

that will include the registers/points accessed through the Head. Use

Executive software M/N 57C300Ć57C303 for DCS 5000 Processors

and M/N 57C304Ć57C307, M/N 57C390Ć57C393, or M/N 57C395Ć

57C397 for AutoMax Processors. See below for more specific

information on configuring the Head. Note that if the Local I/O Head

will be connected to a rail that contains a M/N 45C42 Dual Electronic

Input module, that rail must be plugged into ports 1, 2, or 3 only.

4.1

Local I/O Head withAutoMate 20

Four registers are reserved for configuring the Local I/O Head for use

with an AutoMate 20. These registers and the configuration value to

be written for each are listed below in a sample configuration for four

Local I/O Heads:

4 Local I/O Heads withAutoMate 20

Register

Port#

I/O Type

Configuration

Value

Rail# or

Register

2734

0

LHD

6400

0Ć3

2735

1

LHD

6404

4Ć7

2736

2

LHD

6410

10Ć13

2737

3

LHD

6414

14Ć17

4.2

Local I/O Head withAutoMate 30,

AutoMate 40, or Local I/O Processor

When using the Local I/O Head with the AutoMate 30 or 40, or the

Local I/O Processor, only the first register of the four that are needed

for the configuration needs to be specified. The Executive software

automatically assigns the next three contiguous registers for the

configuration. Note that even if only one port of the Head is being

used, four contiguous registers are still reserved for the configuration.

See below for sample configurations.