2Ć2

TO PROCESSOR, LOCAL I/O PROCESSOR

OR REMOTE HEAD

INPUT

RAIL 0

RAIL 1

RAIL 3

RAIL 2

POWER
COM

RAIL FAULT 0
RAIL FAULT 1
RAIL FAULT 2
RAIL FAULT 3

AutoMate

LOCAL HEAD

61C23

FUSE TYPE

250VAC

AGC 3 AMP

RAIL CONNECTORS

R

+24/48

VDC

COM

Figure 2.2 Ć Local I/O Head (24/48 VDC)

The INPUT connector is used for the Local I/O Interface cable. (+)

and (-) are input power connections. GND is used to connect a

ground wire to earth ground.
The six LEDs on the faceplate are identical for both models. The

LEDs indicate the following:
POWER

The +5VDC supply for the Rails is within limits

COM

There is communication on the Local I/O Interface

cable

RAIL FAULT 0 The Head and Rail 0 are not communicating. An I/O

reset has shut off Rail outputs.

RAIL FAULT 1 The Head and Rail 1 are not communicating. An I/O

reset has shut off Rail outputs.

RAIL FAULT 2 The Head and Rail 2 are not communicating. An I/O

reset has shut off Rail outputs.

RAIL FAULT 3 The Head and Rail 3 are not communicating. An I/O

reset has shut off Rail outputs.