46 FLEX Ex 8 Output and HART Analog Modules

Publication

1797-5.3 - September 2011

FM I/O Entity Parameters for 1797-OE8

FM I/O Entity Parameters for 1797-OE8H

Wiring

Method

Channel Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

μ

F)

L

a

(mH)

1 and 2

Any one

channel

(for

example,

ch0)

0(+), 1(sig)

21.0

100.0

-

-

A, B

0.20

3.5

C, E

0.60

10.5

D, F, G

1.60

28.0

Wiring

Method

Channel Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

μ

F)

L

a

(mH)

1 and 2

Any one

channel

(for

example,

ch0)

0(+), 1(sig)

21.6

92

-

-

A, B

0.164

3.5

C, E

0.49

10.5

D, F, G

1.31

28.0

FLEX Ex Analog
Output I/O

Indicators

Female Bus

Field Wiring

Terminal Base

Terminal Base
Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion

42055