background image

36 FLEX Ex 8 Output and HART Analog Modules

Publication

1797-5.3 - September 2011

Weight

200 g (approximately)

Keyswitch Position

4

Environmental Conditions

Operational Temperature

-20…+70

o

C (-4…+158

o

F)

Storage Temperature

-40…+85

o

C (-40…+185

o

F)

Relative Humidity

5…95% noncondensing

Shock

Operating

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Nonoperating

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Vibration

Tested 2 g @ 10…500 Hz per IEC68-2-6

Agency Certification

CENELEC

II (1) 2G Ex ib[ia] IIC T4

II (1) D [Ex iaD]

UL, C-UL

Class I, Groups A, B, C and D; Class II, Groups E, F and G;
Class III Hazardous Locations

Class I, Zone 1, AEx ib[ia] IIC T4

FM

Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.

Associated Apparatus with intrinsically safe Connections
Class I, II, III, Div 1, Groups A--G

Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.

IECEx

[Zone 0] Ex ib[ia] IIC T4

[Ex iaD]

INMETRO

BR-Ex ia/ib IIB/IIC T4