Configure Scheduled Communications
Objectives
This chapter shows how to configure a sample ControlNet network
using Scheduled messaging between a PanelView Plus/PanelView
Plus CE terminal and an Allen-Bradley controller. It shows how to:
• Configure the PLC ladder logic file
• Configure the ControlNet network using RSNetWorx for
ControlNet
• Configure the RSView Machine Edition application file
Software Requirements
Verify that the correct software/firmware is installed on the
development desktop and PanelView Plus or PanelView Plus CE
terminal.
ControlNet Scheduled Communications
Requirements
PanelView Plus 700-1500
PanelView Plus CE 700-1500
PanelView Plus 400 or 600
RSView Studio
v3.20 or later
v4.0 or later
RSView Machine Edition Runtime
v3.20.04.43 or later
v4.0 or later
RSNetWorx for ControlNet
v5.11 or later
v6.0 or later
RSLogix 5000
v13.0 or later
v15.0 or later
ControlNet Module Firmware
2711P-RN15S, Series A, Rev C
(firmware v3.08 or later)
(1)
2711P-RN15C, Series A, Rev A
or later
(1)
This applies to terminals that are ordered as pre-configured units with the ControlNet module.
ATTENTION
The ControlNet Communications Module (2711P-RN15S) will
not run with RSView ME firmware 3.20.03.43 or earlier. All
ControlNet Modules with v3.07 firmware must be upgraded to
v3.08 or later; otherwise, outputs may turn on an indeterminate
state.