Rockwell Automation 2080-LC30-48AWB_48QWB_48QVB_48QBB Micro830 48 Point LC30 Programmable Controllers User Manual
Page 15
![background image](/manuals/580611/15/background.png)
Micro830 48 Point Programmable Controllers 15
Publication 2080-IN005B-EN-P - April 2014
Enclosure type
rating
Meets IP20
Pilot duty rating
C300, R150
N.A.
Isolation
voltage
250V (continuous),
Reinforced
Insulation Type,
Outputs to Aux and
Network, Inputs to
Outputs
Type tested for
60 s at 3250V DC
I/O to Aux and
Network, Inputs
to Outputs
250V (continuous),
Reinforced
Insulation Type,
Outputs to Aux and
Network, Inputs to
Outputs
Type tested for
60 s at 720V DC,
Inputs to Aux and
Network,
3250V DC Outputs
to Aux and
Network, Inputs
to Outputs
50V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60 s at 720V DC, I/O
to Aux and Network,
Inputs to Outputs
North American
temp code
T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication
Input Specifications
Attribute
2080-LC30-48AWB
2080-LC30-48QWB / 2080-LC30-48QVB /
2080-L30-48QBB
120V AC Input
High-Speed
DC Input
(Inputs 0...11)
Standard DC Input
(Inputs 12 and
higher)
Number of inputs
28
12
16
Input group to backplane
isolation
Verified by the
following dielectric
tests: 1,400V AC for
2 s
132V working
voltage (IEC Class 2
reinforced
insulation)
Verified by the following dielectric tests:
1,414V DC for 2 s
75V DC working voltage (IEC Class 2
reinforced insulation)
Voltage category
110V AC
12/24V sink/source (standard)
24V DC sink/source
Operating voltage
132V, 60 Hz AC, max
16.8…26.4V DC
10…26.4V DC
General Specifications
Attribute
2080-LC30
-48AWB
-48QWB
-48QVB
-48QBB